Conair UGH016/0500 Air Conditioner User Manual


 
The Troubleshooting section covers problems directly related
to the operation and maintenance of the portable chiller. This
section does not provide solutions to problems that originate
with other equipment. Additional troubleshooting help can be
found in manual supplied with the other equipment.
Conditions you may see are:
electrical - a fuse is out, a switch has tripped
mechanical - pump, condenser not working
physical - water flow incorrect
As part of troubleshooting you need to know the status of the
inputs and outputs. Open the electrical enclosure and check
the status of the inputs and outputs. When they are in normal
range, the numbers are highlighted. If the number is not high-
lighted, it is out of range.
UGH016/0500 Series 1 Portable Chillers, TIC Control
TROUBLESHOOTING 6-3
I
DENTIFYING
THE
CAUSE OF
A
PROBLEM
I 123456789 101112
O12345678
DAY
TIME
In this example, inputs 7 and 8 are highlighted; they are in
normal position. The unhighlighted numbers are out of range.
Refer to the wiring diagram and the following table for the
switch status:
Inputs
Outputs
Input
1
2
3
4
5
6
7
8
9
10
11
12
Description
Chiller Stop
Chiller Start
Level Switch
Flow Switch
Compressor Running
Pump Running
Suction Pressure Switch
Discharge Pressure Switch
Low Temperature Deviation
Optional Auto-Fill Level Switch
Pressure Differential Switch
(7.5, 10, 15 ton only)
Optional Alarm Silence
Output
1
2
3
4
5
6
7
8
Description
Compressor Starter
Compressor Run Lamp
Pump Starter
Pump Run Lamp
Alarm Lamp
Optional Auto-Fill Solenoid
Optional Alarm Bell
Optional Alarm Strobe
Always refer to the wiring
diagrams you received
with your chiller to locate
specific electrical compo-
nents.