Conair UGH016/0500 Air Conditioner User Manual


 
The default low temperature limit for the To Process fluid is
set at the factory at 40 °F. This temperature limit is the lowest
temperature for the chilled fluid leaving the Chiller. If you
want to cool fluid below 40 °F (4 °C) and down to 20 °F
(-7 °C), you need to fill the chiller with the proper percentage
of glycol solution. See Filling the Chiller, in the Installation
section.
After the Chiller is filled with the proper percentage of glycol
solution, you need to set the minimum operating temperature
on the control. Use the temperature you chose when selecting
the percent glycol.
To set the To Process low limit on the control:
Press Menu button until INP shows
on the screen.
Press the Enter button until SPLL
displays on the screen. SPLL flashes, along with
the current low limit temperature.
Press the Up/Down arrows
to change the temperature to the required num-
ber.
Press the Menu button
to accept the new temperature.
If you want to change from using a glycol solution back
to using water in your chiller, you need to change the low
limit temperature to 40 °F (4 °C). Follow the steps listed
here to set the To Process low limit to 40.
Series 1 Portable Chillers, TIC Control UGH016/0500
4-8
OPERATION
S
ETTING THE TO
PROCESS LOW
LIMIT
To return to the To Process
Temperature screen from
any other screen, press and
hold the button for at
least 5 seconds until the
temperature displays.
1
2
3
4