Vermont Casting 7PDVS Indoor Fireplace User Manual


 
5
DV Power Vent System
10003262
The DV Power Vent System box needs a minimum 1” clearance all around the box.
The DV Power Vent System box already has a 1” stand-off on all sides.
Pipes from the fireplace to the DV Power Vent System box and from the box to the vent termination need:
Clearance to combustible materials of 1” all around the pipe on vertical sections.
Clearance to combustible materials of 1” on sides and bottom, and 2” on the top of horizontal sections.
Clearance to Combustible Materials and Access Door
Confined Area Access Door Suggestions
12"
Min.
12"
Min.
CFM501
Power vent
min. clearance