Carrier 48/50A020-060 Air Conditioner User Manual


 
2
INSTALLATION
Check Package Contents —
Remove accessory pack-
aging and inspect shipment for damage. If any damage is
found, file a claim with the shipping agent immediately. If any
item is missing or any part does not assemble properly, notify
your Carrier distributor.
Table 1 lists the accessory package contents. Figure 1 shows
the smoke detector.
Table 1 — Accessory Package Contents — Return
Air Smoke Detector (CRSMKDET002C00)
Return Air Smoke Detector Installation
NOTE: For horizontal applications it is easiest to install the
smoke detector prior to making duct connections.
48/50A Units —
The return air smoke detector is to be
installed in the predrilled holes located in the indoor section
above the auxiliary control box.
1. Open the hinged auxiliary control box access door and
secure.
2. Find the 2 plugs located in the partition above the control
box, remove and discard. See Fig. 2.
3. Remove cover from smoke detector. The screws will
remain captured in the cover.
4. Place foam gaskets over each sampling tube on smoke
detector. See Fig. 1.
5. Remove one knockout from top of smoke detector.
6. Insert stripped ends of wire harness through knockout and
wire to smoke detector as shown in Fig. 3. Use ground
screw in the smoke detector to secure a wire tie. Use wire
tie to provide strain relief for the wire harness.
7. Slide smoke detector into holes in partition. Do not secure
at this time.
When installing the smoke detector in the unit, follow all
local codes. Damage to unit may result.
ITEM QUANTITY
Smoke Detector with Cover
1
Sampling Tube (long)
1
Sampling Tube Filters
2
Test Magnet
1
Foam Gaskets
2
Screw, no. 6 Self Tapping
2
Tube End Plug (large)
1
Sampling Tube Support Bracket
1
Screw, 8-18
3
/
4
-in. Pan Head
2
Screw,
1
/
4
AB-14
5
/
8
-in.
2
Snap Bushing
1
Harness Assembly
1
Smoke detector bracket 50ZZ500420
1
Sampling tube bracket 50ZZ500421
1
Sampling tube bracket 50ZZ500431
(48/50Z030-050 with Power Exhaust)
1
Prior to installation of this accessory, make sure all power
is disconnected to the unit and locked out. Failure to dis-
connect power supply prior to servicing may result in seri-
ous injury.
FOAM
GASKETS
CONDUIT HOLES
DETECTOR
HOUSING
TERMINAL STRIP
POWER BOARD
COVER MOUNTING
SCREWS
FILTERS
SAMPLING TUBE
DETECTOR BOARD
DETECTOR COVER
PLASTIC
SAMPLING TUBE
PLASTIC SAMPLING TUBE
SELF-TAPPING SCREW
PHOTO
Fig. 1 — Smoke Detector
SMOKE DETECTOR
MOUNTING PLUGS
PARTITION
PL13
AUXILIARY
CONTROL PANEL
Fig. 2 — Smoke Detector Mounting Location for
48/50A020-060