Carrier 40RMS008-034 Air Conditioner User Manual


 
7
Table 1E — 40RMQ Physical Data, SI — Heat Pump Units
LEGEND
*Units are shipped without refrigerant charge.
UNIT 40RMQ 008 012 016 024 028
NOMINAL CAPACITY (kW) 26 35 52 70 87
OPERATING WEIGHT (kg)
Base Unit with TXV 175 194 323 326 477
Plenum 80 80 102 44 44
FANS
Qty...Diam. (mm) 1...381 1...381 2...381 2...381 2...457
Nominal Airflow (L/s) 1604 1888 2831 3775 4719
Airflow Range (L/s) 1203-2006 1416-2360 2124-3539 2831-4719 3539-5899
Nominal Motor kW (Standard Motor)
208/230-1-60 1.79
208/230-3-60 and 460-3-60 1.79 1.79 2.76 3.73 5.60
575-3-60 1.49 1.49 2.24 3.73 5.60
230-3-50, 400-3-50 1.79 2.16 2.16 3.73 5.60
Motor Speed (r/s)
208/230-1-60 28.8
208/230-3-60 and 460-3-60 28.8 28.8 28.8 29.1 29.1
575-3-60 28.8 28.8 28.8 29.1 29.3
230-3-50, 400-3-50 23.8 23.8 23.8 23.8 23.8
REFRIGERANT R-22
Operating charge (kg)
(approx per circuit)*
1.36 0.91/0.91 1.36/1.36 1.59/1.59 2.04/2.04
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag) 2999
Face Area (sq m) 0.77 0.93 1.85 1.85 2.30
No. of Splits 12222
No. of Circuits per Split 15 9 18 18 24/16
Split Type...Percentage Face...50/50 Face...60/40
Rows...Fins/m 3...591 4...591 4...591 4...591 4...591
STEAM COIL
Max Working Pressure (kPag at 126 C) 138
Total Face Area (sq m) 0.62 0.62 1.24 1.24 1.39
Rows...Fins/m 1...355 1...355 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034
Total Face Area (sq m) 0.62 0.62 1.24 1.24 1.39
Rows...Fins/m 2...335 2...335 2...335 2...335 2...493
Water Volume
(L) 31.4 52.6
(m
3
) 0.031 0.052
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Vapor (ODF) 1...1
1
/
8
2...1
1
/
8
2...1
1
/
8
2...1
3
/
8
DX Coil — Liquid Refrigerant (ODF) 1...
5
/
8
2...
5
/
8
2...
5
/
8
Steam Coil, In (MPT) 1...2
1
/
2
1...2
1
/
2
1...2
1
/
2
Steam Coil, Out (MPT) 1...1
1
/
2
1...1
1
/
2
1...1
1
/
2
Hot Water Coil, In (MPT) 1...1
1
/
2
1...1
1
/
2
1...2
Hot Water Coil, Out (MPT) 1...1
1
/
2
1...1
1
/
2
1...2
Condensate (Male PVC) 1...1
1
/
4
ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size
4...406 x 610 x 51
4...406 x 508 x 51
4...406 x 610 x 51
4...406 x 610 x 51
4...406 x 508 x 51
4...406 x 610 x 51
4...508 x 635 x 51
Access Location Either Side Right or Left Side
DX Direct Expansion
TXV Thermostatic Expansion Valve