Fig. 2—Unit Reference Drawing
→ Dimensions (In.)
UNIT
SIZE
SERIES
UNIT DIMENSIONS
MINIMUM MOUNTING
PAD DIMENSIONS
A B C D E F G H J K L M Support Feet Snow Stand
024 1 33-13/16 30 34-15/16 4 9-3/4 21-1/2 27-7/8 5/8 8-3/16 16-13/16 20-1/2 14 26 X 32 31 X 35
030 1 39-13/16 30 34-15/16 4 9-3/4 27-1/2 33-7/8 3/4 8-3/16 16-1/2 20-3/8 15 26 X 32 31 X 35
036 1 39-13/16 30 34-15/16 4 9-3/4 27-1/2 33-7/8 3/4 8-3/16 16-1/2 20-3/8 16 26 X 32 31 X 35
042 1 39-13/16 30 34-15/16 4 9-3/4 27-1/2 33-7/8 7/8 8-3/16 16-1/2 20-3/8 15 26 X 32 31 X 35
048 1 33-13/16 38-5/8 45 5-5/16 11-13/16 21-1/2 27-7/8 7/8 8-9/16 19-1/2 25-1/2 16 34 X 42 36 X 46
A96517
2
1
/2
"
1
9
/16
"
AIR DISCHARGE
4
3
/16
"
3
/8 IN.
DIA.
LIQUID LINE
CONN
1
3
/4
"
2
15
/16
"
FIELD POWER SUPPLY CONN
7
/8 IN.
DIA HOLE WITH
1
1
/8 IN. DIA KNOCKOUT
AND
1
3
/8 IN. DIA KNOCKOUT
10
1
/2
"
F
G
A
FIELD CONTROL SUPPLY
CONN
7
/8 IN.
DIA HOLE
AIR DISCHARGE
AIR DISCHARGE
AIR IN
AIR IN
AIR IN
H DIA VAPOR LINE CONN
3
/8 IN. DIA TIEDOWN
KNOCKOUTS (2)
PLACES IN BASEPAN
B
1
1
/4
"
M
ACCESS
PANEL
L
K
C
D
E
J
C
L
1. Allow 30 in.
clearance to service side of unit, 48 in. above unit, 6 in.
on one side, 12 in. on remaining side, and 24 in. between units for proper airflow.
Minimum outdoor operating ambient in cooling mode is 55°F (unless low ambient control is used) max 125°F.2.
Maximum outdoor operating ambient in heating mode is 66°F.3.
Series designation is the 13th position of the unit model number.4.
Center of gravity .5.
NOTES:
2