Carrier 13 50XP Fan User Manual


 
14
50XP
Performance data (cont)
ECONOMIZER 1-in. FILTER PRESSURE DROP (in. wg)
MULTIPLICATION FACTORS
Example: 15.0 kW (at 240v) heater on 208 v
= 15.0 (.75 mult factor)
= 11.25 capacity at 208 v
UNIT50XP PRESSURE DROP
024-036 0.20
042-060 0.25
HEATER kW
RATING
VOLTAGE
DISTRIBUTION
MULTIPLICATION
FACTOR
240
200
208
230
240
.69
.75
.92
1.00
ELECTRIC HEAT PRESSURE DROP TABLES
Small Cabinet: 024-036
Large Cabinet: 042-060
STATIC
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
5 kW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02 0.04 0.06 0.07
7.5 kW 0.00 0.00 0.00 0.00 0.00 0.00 0.02 0.03 0.05 0.07 0.08 0.09
10 kW 0.00 0.00 0.00 0.00 0.00 0.02 0.04 0.06 0.07 0.09 0.10 0.11
15 kW 0.00 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18
STATIC
CFM
1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
5 kW 0.00 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12
7.5 kW 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13
10 kW 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13
15 kW 0.00 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15
20 kW 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16
FILTER PRESSURE DROP (In. wg)
FILTER SIZE
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
20 X 20 X 1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15
20 X 24 X 1 ————0.09 0.10 0.11 0.13 0.14 0.15 0.16
24 X 30 X 1 ———————0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18