Bryant T6-NAC Thermostat User Manual


 
45
Relays
This thermostat uses latching relays. When the thermostat loses power, the relays
will remain in their last position until power is restored and all relays are reset to
their correct position. Out of the box, the outputs may appear to be On when the
thermostat is not powered. This is normal. Output states should only be checked
when the thermostat is powered.
Temperature Offset After Power Cycle
To compensate for internal heat buildup from the electronics in the thermostat,
the thermostat will add an offset to the actual temperature that it measures. If the
thermostat power is cycled quickly, one can witness an immediate increase in the
actual temperature displayed due to this added offset. The thermostat display will
return to the actual room temperature after several minutes of operation.
TROUBLESHOOTING
If the display module doesn’t power up after power is applied, check the Rc/Rh
and C terminals for 24VAC. If 24VAC is present, check the voltage between Vg
and V+. This voltage will be approximately 1220VDC. If voltage is present,
check the polarity to make sure it is wired correctly. The display will not power
up if polarity is reversed.
If dashes appear for Option 01 in config and during reboot, the problem could be
the red pigtail being wired to Rc or Rh and the black pigtail being wired to C. If
so, remove the twowire pigtail and connect to the V+ and Vg terminals.
Error Codes
−− If AC/HP Control cannot properly read room temperature, display will
indicate “−−” and all outputs (except fan, if on) will turn off. In the case where
the installer has selected to average the local sensor and the remote room sensor,
the AC/HP display will alternate between “−−” for the failed sensor and the