Bryant R-410A Air Conditioner User Manual


 
—2—
DIMENSIONS
AIR DISCHARGE
AIR DISCHARGE
AIR IN
AIR IN
AIR IN
3
/8" DIA. TIEDOWN KNOCKOUTS
(2) PLACES
L
K
J
E
D
C
L
NOTES:
1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE
SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 55°F,
(UNLESS LOW AMBIENT CONTROL IS USED) MAX. 125°F.
3. SERIES DESIGNATION IS THE 14TH POSITION OF THE UNIT MODEL NUMBER.
4. CENTER OF GRAVITY .
ACCESS
PANEL
1
1
/4"
2
1
/2"
AIR DISCHARGE
1
3
/4"
4
3
/16"
3
/8" DIA. LIQUID
LINE CONN.
H DIA. VAPOR
LINE CONN.
7
/8" DIA. HOLE
FIELD POWER SUPPLY CONN.
7
/8" DIA.
HOLE WITH 1
1
/8" DIA. KNOCKOUT
AND 1
3
/8" DIA. KNOCKOUT
10
1
/2"
FIELD CONTROL
SUPPLY CONN
1
9
/16"
C
F
N
G
A
B
M
A99067
DIMENSIONS (IN.)
UNIT
SIZE SERIES
UNIT DIMENSIONS MINIMUM
MOUNTING
PAD DIMENSIONSABCDEFGHJKLMN
018 A 23-13/16 22-1/2 27-1/2 2-13/16 6-15/16 13-15/16 18-3/8 5/8 8-3/16 12-1/2 14 16-1/2 2-3/8 20 x 32
024 A 27-13/16 22-1/2 27-1/2 2-13/16 6-15/16 15-15/16 22-3/8 5/8 8-3/16 12-1/2 14 16-1/2 2-15/16 20 x 32
030 A 27-13/16 22-1/2 27-1/2 2-13/16 6-15/16 15-15/16 22-3/8 3/4 8-3/16 12-1/2 14 16-1/2 2-15/16 20 x 32
036 A 33-13/16 22-1/2 27-1/2 2-13/16 6-15/16 21-15/16 28-3/8 3/4 8-3/16 12-1/2 14 17-1/2 2-15/16 20 x 32
042 A 27-13/16 30 33 5-1/16 9-11/16 15-15/16 22-3/8 7/8 8-3/16 18-1/2 19-3/4 13 2-15/16 26 x 32
048 A 27-13/16 30 33 5-1/16 9-11/16 15-15/16 22-3/8 7/8 8-3/16 18-1/2 19-3/4 13 2-15/16 26 x 32
060 A 39-13/16 30 33 5-1/16 9-11/16 27-15/16 34-3/8 7/8 8-3/16 17-3/4 19 17-3/4 2-15/16 26 x 32