BASE UNIT DIMENSIONS — 579F180,216
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
•Rear: 7-0 (2134) for coil removal. This dimension can be reduced to
4-0 (1219) if conditions permit coil removal from the top.
•4-0 (1219) to combustible surfaces, all four sides (includes between
units).
Left side: 4-0 (1219) for proper condenser coil airflow.
Front: 4-0 (1219) for control box access.
• Right side: 4-0 (1219) for proper operation of damper and power
exhaust if so equipped.
•Top: 6-0 (1829) to assure proper condenser fan operation.
Bottom: 14 (356) to combustible surfaces (when not using curb).
Control box side: 3-0 (914) to ungrounded surfaces, non-combustible.
Control box side: 3-6 (1067) to block or concrete walls, or other
grounded surfaces.
Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and the damper/
power exhaust as stated in Note #6, a removable fence or barricade
requires no clearance.
8. Dimensions are from outside of corner post. Allow 0-
5
/
16
(8) on each side
for top cover drip edge.
9. See drawing 50TJ500352 for service option details.
UNIT
579F
STD UNIT
WEIGHT
ECONOMIZER
WEIGHT
CORNER
A
CORNER
B
CORNER
C
CORNER
D
DIM A DIM B DIM C
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm
180 1650 748 90 41 423 192 386 175 403 183 438 199 3-5 1041 3-5 1041 1-10 559
216 1800 816 90 41 432 196 410 186 461 209 472 214 3-3 991 3-7 1092 1-8 508
a48-7338
579F180-300