Bryant 581C Gas Heater User Manual


 
102
PERFORMANCE DATA (cont)
COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)
LEGEND
*Negative SHC value indicates that the air entering the coil is being
heated.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
Where: h
ewb
= Enthalpy of air entering evaporator coil.
3. The SHC is based on 80 F edb temperature of air entering evapo-
rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
581B072 (6 TONS) — SUBCOOLING MODE
Temp (F)
Air Ent
Condenser
(Edb)
Air Entering Evaporator — Cfm/BF
1800/0.05 2100/0.06 2400/0.06 3000/0.08
Air Entering Evaporator — Ewb (F)
72 67 62 72 67 62 72 67 62 72 67 62
75
TC 82.6 75.6 68.5 84.9 78.0 70.9 85.9 79.5 73.5 89.1 82.7 77.0
SHC 36.0 44.8 55.4 37.5 49.1 59.7 38.8 51.1 64.0 41.8 58.1 70.2
kW 4.60 4.52 4.36 4.67 4.57 4.46 4.70 4.57 4.45 4.77 4.61 4.51
85
TC 78.2 71.6 64.5 80.9 73.4 65.8 82.0 74.4 67.9 85.8 78.2 72.3
SHC 31.4 41.2 51.7 33.0 44.7 55.8 34.7 47.4 60.1 37.6 54.3 66.7
kW 5.16 5.03 4.89 5.22 5.11 4.96 5.26 5.09 4.97 5.32 5.17 5.04
95
TC 73.8 67.4 60.2 76.3 68.3 60.5 77.5 69.3 62.3 82.0 72.8 67.5
SHC 27.0 37.6 47.9 28.2 40.0 51.6 30.2 43.7 56.2 33.6 49.2 62.9
kW 5.75 5.60 5.44 5.80 5.66 5.48 5.84 5.68 5.53 5.90 5.73 5.60
105
TC 68.4 62.6 55.9 71.4 64.3 56.2 72.1 64.6 58.3 75.7 67.0 62.4
SHC 22.3 33.5 43.5 23.4 36.5 48.0 25.4 38.4 50.2 29.1 45.2 56.2
kW 6.37 6.22 6.06 6.45 6.27 6.10 6.46 6.29 6.16 6.53 6.36 6.24
115
TC 63.4 57.8 50.7 66.0 60.1 51.5 66.4 59.6 54.5 68.8 60.8 57.5
SHC 18.1 29.5 38.9 18.8 32.9 44.1 20.7 33.3 43.8 24.3 41.4 49.7
kW 7.04 6.89 6.68 7.10 6.91 6.74 7.12 6.95 6.83 7.16 7.01 6.92
125
TC 55.5 49.6 45.8 58.4 52.4 46.1 57.6 52.1 49.5 59.2 52.8 53.1
SHC 15.3 24.0 35.2 15.7 27.5 39.0 17.5 27.5 38.4 20.9 34.6 44.4
kW 7.80 7.61 7.38 7.83 7.67 7.49 7.89 7.72 7.58 7.92 7.78 7.70
581B072 (6 TONS) — HOT GAS REHEAT MODE*
Temp (F)
Air Ent
Condenser
(Edb)
Air Entering Evaporator — Ewb (F)
75 Dry Bulb
62.5 Wet Bulb
(50% Relative)
75 Dry Bulb
64 Wet Bulb
(55% Relative)
75 Dry Bulb
65.3 Wet Bulb
(60% Relative)
Air Entering Evaporator — Cfm
1800 2100 2400 1800 2100 2400 1800 2100 2400
80
TC 27.41 28.12 28.75 27.25 27.98 28.62 27.12 27.86 28.51
SHC 5.74 7.61 9.25 1.68 3.52 5.14 –1.85 –0.03 1.58
kW 4.40 4.39 4.39 4.44 4.44 4.44 4.49 4.49 4.49
75
TC 27.98 28.66 29.24 27.89 28.58 29.18 27.81 28.52 29.13
SHC 5.73 7.48 9.02 1.92 3.65 5.18 –1.38 0.34 1.85
kW 4.45 4.45 4.45 4.50 4.50 4.50 4.55 4.55 4.55
70
TC 28.55 29.19 29.74 28.53 29.18 29.74 28.51 29.17 29.74
SHC 5.71 7.35 8.79 2.17 3.79 5.22 –0.91 0.70 2.12
kW 4.51 4.51 4.51 4.57 4.57 4.57 4.62 4.62 4.62
60
TC 29.70 30.25 30.74 29.80 30.37 30.86 29.89 30.47 30.97
SHC 5.67 7.09 8.34 2.65 4.06 5.29 0.04 1.43 2.65
kW 4.62 4.62 4.62 4.69 4.69 4.69 4.75 4.75 4.75
50
TC 30.84 31.32 31.73 31.07 31.56 31.98 31.27 31.77 32.20
SHC 5.63 6.83 7.89 3.14 4.33 5.37 0.98 2.15 3.19
kW 4.74 4.74 4.74 4.82 4.82 4.82 4.89 4.89 4.89
40
TC 31.99 32.38 32.73 32.35 32.75 33.12 32.66 33.07 33.43
SHC 5.60 6.57 7.43 3.63 4.59 5.44 1.92 2.88 3.72
kW 4.86 4.86 4.86 4.95 4.95 4.95 5.02 5.02 5.02
BF Bypass Factor
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW Compressor Motor Power Input
SHC Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm
581B036-150