Bryant 581C Gas Heater User Manual


 
135
PERFORMANCE DATA (cont)
EVAPORATOR-FAN MOTOR PERFORMANCE — STANDARD MOTOR
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the
motors can be utilized with confidence. Using fan motors up to the ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not be affected.
EVAPORATOR-FAN MOTOR PERFORMANCE — HIGH-STATIC MOTOR
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the
motors can be utilized with confidence. Using fan motors up to the ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not be affected.
UNIT
581B
UNIT
VOLTAGE
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
MAXIMUM
AMP DRAW
036
208/230 Single 1.20 1000 4.9
208/230
Three 1.20 1000
4.9
460 2.2
575 2.2
048
208/230 Single 1.20 1000 4.9
208/230
Three 1.20 1000
4.9
460 2.2
575 2.2
060
208/230 Single 1.30 1650 10.1
208/230
Three 2.40 2120
6.7
460 3.0
575 3.0
072
208/230
Three 2.40 2120
6.7
460 3.0
575 3.0
090,102
208/230
Three 2.90 2615
8.6
460 3.9
575 3.9
120
208/230
Three 3.70 3775
12.2
460 5.5
575 5.5
150
208/230
Three 5.25 4400
17.3
460 8.5
575 8.5
UNIT
581B
UNIT
VOLTAGE
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
MAXIMUM
AMP DRAW
036
208/230
Three 2.40 2120
6.7
460 3.0
575 3.0
048
208/230
Three 2.40 2120
6.7
460 3.0
575 3.0
060
208/230
Three 2.90 2615
8.6
460 3.9
575 3.9
072
208/230
Three 2.90 2615
8.6
460 3.9
575 3.9
090,102
208/230
Three 4.20 3775
12.2
460 5.5
575 5.5
120
208/230
Three 5.25 4400
17.3
460 8.5
575 8.5
581B036-150