Bryant 581B Gas Heater User Manual


 
48
ELECTRICAL DATA (cont)
581B090-120 HIGH-STATIC MOTOR (Units Without Electrical Convenience Outlet)
581B090-120 HIGH-STATIC MOTOR (Units With Electrical Convenience Outlet)
LEGEND
*Used to determine minimum disconnect per NEC.
Fuse or HACR circuit breaker per NEC.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker. The
UL, Canada approved units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.
% Voltage imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT:
If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
UNIT
581B
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE*
Min Max RLA LRA FLA FLA RLA MCA MOCP FLA LRA
090
208/230-3-60 187 254 12.4 88.0 1.4 10.6 0.6 41.3 45 44 267
460-3-60 414 508 6.4 44.0 0.7 4.8 0.3 20.6 25 22 134
575-3-60 518 632 4.8 34.0 0.7 4.8 0.3 15.8 20 17 95
102
208/230-3-60 187 254 15.0 99.0 1.4 10.6 0.6 47.2 60 50 264
460-3-60 414 508 8.2 49.5 0.7 4.8 0.3 24.7 30 26 132
575-3-60 518 632 5.8 40.0 0.7 4.8 0.3 18.0 20 19 107
120
208/230-3-60 187 254 17.3 125.0 1.4 15.0 0.6 56.7 70 61 360
460-3-60 414 508 9.0 62.0 0.7 7.4 0.3 29.1 35 29 181
575-3-60 518 632 7.1 50.0 0.7 7.4 0.3 23.0 25 23 136
UNIT
581B
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE*
Min Max RLA LRA FLA FLA RLA MCA MOCP FLA LRA
090
208/230-3-60 187 254 12.4 88.0 1.4 10.6 0.6 47.3 50 49 267
460-3-60 414 508 6.4 44.0 0.7 4.8 0.3 23.3 25 24 134
575-3-60 518 632 4.8 34.0 0.7 4.8 0.3 18.5 20 19 95
102
208/230-3-60 187 254 15.0 99.0 1.4 10.6 0.6 53.2 60 55 264
460-3-60 414 508 8.2 49.5 0.7 4.8 0.3 27.4 30 28 132
575-3-60 518 632 5.8 40.0 0.7 4.8 0.3 20.7 25 21 107
120
208/230-3-60 187 254 17.3 125.0 1.4 15.0 0.6 62.7 70 66 360
460-3-60 414 508 9.0 62.0 0.7 7.4 0.3 31.8 35 32 181
575-3-60 518 632 7.1 50.0 0.7 7.4 0.3 25.7 30 25 147
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
NEC
National Electrical Code
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
UL
Underwriters Laboratories
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
7
457