Bryant 581B Gas Heater User Manual


 
13
BASE UNIT DIMENSIONS
UNIT
581B
STANDARD
UNIT
WEIGHT
DURABLADE
ECONOMIZER
WEIGHT
ECONOMI$ER
WEIGHT
CORNER
WEIGHT
(A)
CORNER
WEIGHT
(B)
CORNER
WEIGHT
(C)
CORNER
WEIGHT
(D)
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
036
530 240 34 15.4 47 21.3 127 57.6 122 55.3 138 62.6 143 64.9
048
540 245 34 15.4 47 21.3 129 58.5 124 56.2 141 64.0 146 66.2
060
560 254 34 15.4 47 21.3 134 60.8 129 58.5 146 66.2 151 68.5
072
615 279 34 15.4 47 21.3 147 66.7 142 64.4 160 72.6 166 75.3
CONNECTION SIZES
A
1
3
/
8
″″
Dia [35] Field Power Supply Hole
B
2
″″
Dia [51] Power Supply Knockout
C
1
3
/
4
″″
Dia [44] Charging Port Hole
D
7
/
8
″″
Dia [22] Field Control Wiring Hole
E
3
/
4
″″
-14 NPT Condensate Drain
F
1
/
2
″″
-14 NPT Gas Connection
G
2
1
/
2
″″
Dia [64] Power Supply Knockout
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal
discharge units, field-supplied flanges should be attached to horizontal discharge openings, and
all ductwork should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces, 48 inches.
b. Bottom of unit to combustible surfaces (when not using curb), 1 inch.
Bottom of base rail to combustible surfaces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the
greater clearance is optional.
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC (National Electrical Code).
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control box side,
42 in. per NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion side as stated in
notes 5a, b and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering
material if set on base rail.
8. The vertical center of gravity is 1
-6
[457] up from the bottom of the base rail.
BOTTOM POWER CHART, THESE HOLES REQUIRED FOR
USE WITH ACCESSORY PACKAGES CRBTMPWR001A00,
3A00 (
1
/
2
,
3
/
4
) OR CRBTMPWR002A00, 4A00 (
1
/
2
, 1
1
/
4
)
*Select either
3
/
4
or 1
1
/
4
for power, depending on wire size.
THREADED
CONDUIT SIZE
WIRE
USE
REQURED
HOLE SIZES (MAX.)
1
/
2
″″
24 V
7
/
8
[22.2]
3
/
4
″″
Power* 1
1
/
8
[28.4]
1
1
/
4
″″
Power* 1
3
/
4
[44.4]
(003)
1
/
2
″″
FPT
Gas 1
1
/
4
[31.8]
(004)
3
/
4
″″
FPT
Gas 1
5
/
8
[41.3]
581B036-072