42
PERFORMANCE DATA (cont)
EVAPORATOR-FAN MOTOR DATA — HIGH-STATIC MOTORS
LEGEND
Bhp —
Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full
horsepower and watts range of the motors can be utilized with confidence.
Using your fan motors up to the ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not be
affected.
UNIT
581B
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
UNIT VOLTAGE
MAXIMUM
AMP DRAW
036
Three 2.40 2120
208/230 6.7
460 3.0
575 3.0
046
Three 2.40 2120
208/230 6.7
460 3.0
575 3.0
060
Three 2.90 2615
208/230 8.6
460 3.9
575 3.9
072
Three 2.90 2615
208/230 8.6
460 3.9
575 3.9
090,102
Three 4.20 3775
208/230 12.2
460 5.5
575 5.5
120
Three 5.25 4400
208/230 17.5
460 8.5
575 8.5
Durablade Economizer Barometric Relief
Damper Characteristics — 581B036-072
Durablade Economizer Barometric Relief
Damper Characteristics — 581B090-150