Bryant 569J Air Conditioner User Manual


 
7
PHYSICAL DATA (CONT.)
Dual Circuit Models with NOVATION --- All Aluminum Coil Design
569J*12D 569J*14D 569J*16D
Refrigeration System
# Circuits / # Comp. / Type 2/2/Scroll 2/2/Scroll 2/2/Scroll
R---410A charge A/B (lbs) 3.0 /3.1 3.7/3.9 6.1/6.1
System charge w/ fan coil 7.4 / 7.4 10.8 / 10.8 12.0/12.0
Metering device TXV TXV TXV
High---press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505
Low---press. Trip / Reset (psig) 54 / 117 54 / 117 54 / 117
Cond. Coil
Material (Fin/Tube)
Al/Al Al/Al Al/Al
Coil type Novation Novation Novation
Rows / FPI 1 / 20.3 1 / 20.3 1 / 20.3
Total face area (ft2) 25.0 31.8 25.0 x 2
Cond. fan / motor
Qty / Mo tor drive type 2/direct 2/direct 3/direct
Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100
Fan diame ter (in) 22 22 22
Nominal Airflow (cfm) 6,000 6,000 10,000
Watts (total) 610 610 970
Note: 569J*25D model is not available with NOV A TION coil.
Dual Circuit Models with RTPF --- Round Tube/Plate Fin Coil Design
569J*12D 569J*14D 569J*16D 569J*25D
Refrigeration System
# Circuits / # Comp. / Type 2/2/Scroll 2/2/Scroll 2/2/Scroll 2/2/Scroll
R---410a charge A/B (lbs) 8.0 / 8.0 16.0 / 16.0 16.0 / 16.0 14.0 / 14.0
System charge w/ fan coil* 11.0 / 11.0 22.0 / 22.0 22.0 / 22.0 19.0 / 19.0
Metering device TXV TXV TXV TXV
High---press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505 630 / 505
Low---press. Trip / Reset (psig) 54 / 117 54 / 117 54 / 117 54 / 117
Cond. Coil
Material (Fin/Tube) Al/Cu Al/Cu Al/Cu Al/Cu
Coil type RTPF RTPF RTPF RTPF
Rows / FPI 2/17 3/17 2/17 2/17
total face area (ft2) 25.1 31.8 23.5 x 2 25.0 x 2
Cond. fan / motor
Qty / Mo tor drive type 2/direct 2/direct 3/direct 4/direct
Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100
Fan diame ter (in) 22 22 22 22
Nominal Airflow (cfm) 6,000 6,000 9,000 12,000
Watts (total) 610 610 970 1150
* Approximate system charge with about 25 ft piping of sizes indicated with matched 524J