Bryant 569J Air Conditioner User Manual


 
43
ELECTRICAL DATA
569J*07A COOLING WITHOUT POWERED CONVENIENCE OUTLET
V --- Ph --- Hz
VOLTAGE RANGE COMP 1 OFM (ea) POWER SUPPLY
MIN MAX RLA LRA WATTS FLA MCA Fuse
208/230---3---60 187 253 19 123 325 1.5 26.8 45
460 --- 3 --- 6 0 414 506 9.7 62 325 0.8 13.7 20
575 --- 3 --- 6 0 518 633 7.4 50 325 0.7 10.7 15
569J*07A COOLING WITH POWERED CONVENIENCE OUTLET
V --- Ph --- Hz
VOLTAGE RANGE COMP 1 OFM (ea) POWER SUPPLY
MIN MAX RLA LRA WATTS FLA MCA Fuse
208/230---3---60 187 253 19 123 325 1.5 31.6 50
460 --- 3 --- 6 0 414 506 9.7 62 325 0.8 15.9 25
575 --- 3 --- 6 0 518 633 7.4 50 325 0.7 12.4 15
569J*08A COOLING WITHOUT POWERED CONVENIENCE OUTLET
V --- Ph --- Hz
VOLTAGE RANGE COMP 1 OFM (ea) POWER SUPPLY
MIN MAX RLA LRA WATTS FLA MCA Fuse
208/230---3---60 187 253 25 164 325 1.5 34.3 50
460 --- 3 --- 6 0 414 506 12.2 100 325 0.8 16.9 25
575 --- 3 --- 6 0 518 633 9.0 78 325 0.7 12.7 20
569J*08A COOLING WITH POWERED CONVENIENCE OUTLET
V --- Ph --- Hz
VOLTAGE RANGE COMP 1 OFM (ea) POWER SUPPLY
MIN MAX RLA LRA WATTS FLA MCA Fuse
208/230---3---60 187 253 25 164 325 1.5 39.1 60
460 --- 3 --- 6 0 414 506 12.2 100 325 0.8 19.1 30
575 --- 3 --- 6 0 518 633 9.0 78 325 0.7 14.4 20
569J