Bryant 502A Air Conditioner User Manual


 
7
PERFORMANCE DATA (cont)
GROSS COOLING CAPACITIES (cont)
LEGEND
NOTES:
1. Performance based on nominal condenser airflow listed in physical data table
on page 3.
2. SHC is based on 80 F db temperature of air entering the coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 BF) x db 80)
The following formulas may be used:
Where:
h
ewb
= Enthalpy of air entering evaporator coil
EVAPORATOR FAN PERFORMANCE
LEGEND
*Standard direct drive indoor (evaporator) fan motor (IFM). For optional
belt drive IFM performance, see table on page 8.
NOTES:
1. Above fan performance is based on wet coil and deducted casing
losses, and clean factory-installed permanent cleanable filter.
2. Evaporator fans are direct drive (except 048, 060 special order
evaporator-fan motor option). Refer to Belt Drive Evaporator Fan
Performance table on page 8.
3. Interpolation is permissible, do not extrapolate.
4. For units installed with accessory electric heaters, see Electric
Heater Static Pressure Drop table for additional performance losses.
502A048
Temp
Air Ent
Condenser
(F)
Evaporator Air Quantity Cfm/BF
1200/0.06 1600/0.08 2000/0.10
Evaporator Air Ewb Temp (F)
72 67 62 57 72 67 62 57 72 67 62 57
85
TC
56.0 52.1 47.9 44.4 57.7 54.5 50.6 49.6 59.4 56.0 52.7 52.3
SHC
27.8 34.8 41.6 44.4 30.2 39.6 48.0 49.6 32.8 43.9 52.5 52.3
kW
3.77 3.68 3.59 3.53 3.81 3.74 3.66 3.64 3.85 3.77 3.70 3.69
95
TC
54.0 50.1 45.7 42.4 55.7 52.3 48.6 47.3 57.4 53.8 51.0 50.9
SHC
27.1 34.0 40.4 42.4 29.6 38.8 47.0 47.3 32.4 43.2 50.9 50.9
kW
4.21 4.11 4.01 3.95 4.25 4.18 4.09 4.07 4.31 4.21 4.15 4.15
105
TC
51.8 47.9 42.3 40.2 53.6 50.0 45.1 45.0 54.6 51.4 48.9 48.6
SHC
26.3 33.1 38.8 40.2 29.0 38.0 44.8 45.0 31.3 42.4 48.9 48.6
kW
4.69 4.58 4.45 4.40 4.75 4.65 4.54 4.53 4.77 4.69 4.63 4.63
115
TC
49.5 45.5 38.6 37.7 51.2 47.6 41.9 42.1 52.2 49.1 45.8 45.8
SHC
25.5 32.2 37.0 37.7 28.3 27.3 41.8 42.1 30.7 42.0 45.8 45.8
kW
5.21 5.09 4.92 4.89 5.27 5.17 5.03 5.03 5.30 5.23 5.14 5.14
BF
Bypass Factor
Ewb
Entering Wet-Bulb
kW
Compressor Motor Power Input (kilowatts)
SHC
Gross Sensible Heat Capacity (1000 Btuh)
TC
Gross Total Cooling Capacity (1000 Btuh)
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMPERATURE (F)
79 78 77 76 75 Under 75
81 82 83 84 85 Over 85
Correction Factor
.025
1.07 2.12 3.19 4.25 5.32
Use formula
shown below
.05
1.04 2.07 3.11 4.14 5.18
.10
.98 1.96 2.94 3.92 4.90
.20
.87 1.74 2.62 3.49 4.36
.30
.76 1.53 2.29 3.05 3.82
.35
.71 1.42 2.13 2.83 3.54
502A060
Temp
Air Ent
Condenser
(F)
Evaporator Air Quantity Cfm/BF
1500/0.06 2000/0.09 2250/0.10
Evaporator Air Ewb Temp (F)
72 67 62 72 67 62 72 67 62
85
TC
64.8 58.5 52.9 68.0 61.5 56.3 68.9 62.5 58.0
SHC
33.2 41.1 48.5 37.2 47.3 55.7 38.9 50.0 57.7
kW
4.49 4.29 4.13 4.59 4.83 4.22 4.62 4.41 4.27
95
TC
61.9 55.7 50.2 65.1 58.7 54.0 66.1 59.7 55.8
SHC
32.3 40.1 47.3 36.4 46.5 54.0 38.2 49.3 55.8
kW
4.94 4.72 4.57 5.04 4.81 4.67 5.07 4.84 4.72
105
TC
58.5 52.4 47.2 61.5 55.2 51.4 62.6 56.3 53.3
SHC
31.1 38.8 45.8 35.2 45.2 51.4 37.1 48.1 58.2
kW
5.41 5.20 5.04 5.51 5.28 5.16 5.55 5.32 5.22
115
TC
54.9 49.0 44.1 57.8 51.7 48.7 58.7 52.6 50.4
SHC
29.8 37.5 44.0 34.0 43.9 48.7 35.9 46.7 50.4
kW
5.93 5.72 5.56 6.04 5.80 5.70 6.07 5.83 5.75
t
ldb
=t
edb
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air leaving
evaporator col (h
lwb
).
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm
CFM
UNIT SIZE 502A
024 036 048* 060*
ESP Fan kW ESP Fan kW ESP Fan kW ESP Fan kW
600
.60 .20 ——————
700
.54 .22 ——————
800
.43 .24 ——————
900
.29 .26 .69 .44 ————
1000
.11 .29 .57 .46 ————
1100
——.42 .49 1.10 .45 1.11 .52
1200
——.23 .52 1.01 .49 1.045 .55
1300
————.90.51 .97.57
1400
————.79.55 .88.59
1500
————.67.58 .78.62
1600
————.54.61 .67.64
1700
————.39.64 .53.67
1800
————.22.67 .52.70
1900
————.03.70 .40.74
2000
——————.28 .78
ESP
External Static Pressure (in. wg)
kW
Total Fan Motor Power Input (kilowatts)