Bryant 359AAV Furnace User Manual


 
5
CELL PANEL
BURNERS
BURNER BOX
MANIFOLD
GAS VALVE
A07826
Fig. 4 -- Burner Box Assembly
4. Remove wires from gas valve. Note location for reassembly.
5. Unplug igniter from harness.
6. Remove screws that secure manifold to burner box.
(See Fig. 4.)
NOTE: Do not remove burner box from cell panel.
7. Remove manifold, orifices, and gas v alve as 1 assembly.
8. Remove screws attaching burner assembly in burner box.
NOTE: Use care when removing and reinstalling burners not to
strike the hot surface igniter.
9. Remove burner assembly from burner box.
NOTE: All burners are attached to burner bracket and can be
removed as 1 assembly.
10. Clean burners with soft brush and vacuum.
11. Reinstall manifold, orifice, and gas valve assembly in
burner box. Ensure burners fit over orifices.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Igniter wires must be securely placed in slot in manifold
grommet or else they could become pinched or severed and
electrically shorted.
!
WARNING
12. Reconnect wires to gas valve and igniter. Refer to furnace
wiring diagram for proper wire location.
13. Reinstall gas supply pipe to furnace gas control valve using
backup wrench on gas valve to prevent rotation and
improper orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks.
DO NOT use T eflon tape.
FIRE, EXPLOSION, UNIT DAMAGE HAZARD
Failure to follow this warning could result in property damage,
personal injury, or death.
Gas valve switch MUST be facing forward or tilted upward.
!
WARNING
14. Turn on gas and electrical supplies to furnace.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings could result in personal
injury, death, or property damage.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the
detection of leaks to check all connections.
!
WARNING
15. Check for gas leaks.
16. Replace main furnace door.
PRIMAR
Y
HX
INLET OPENINGS
A07827
Fig. 5 -- Cleaning Inlet Openings of Primary Heat Exchangers
359AAV