GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor-- mounted, air --cooled, split-- system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, propeller--type
condenser fan, and a control box. Unit will discharge supply
air upward as shown on contract drawings. Unit will be used in
a refrigeration circuit to match up to a packaged fan coil or coil
unit.
Quality Assurance
Unit will be rated in accordance with the latest edition
of ARI Standard 240.
Unit will be certified for capacity and efficiency, and
listed in the latest ARI directory.
Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
Unit will be constructed in accordance with UL
standards and will carry the UL label of approval.
Unit will have C--UL approval.
Unit cabinet will be capable of withstanding Federal
Test Method Standard No. 141 (Method 6061) 500--hr
salt spray test.
Air--cooled condenser coils will be leak tested at 217
psig and pressure tested at 450 psig.
Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
Unit will be shipped as single package only a nd is
stored and handled per unit manufacturer’s
recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.
PRODUCTS
Equipment
Factory assembled, single piece, air--cooled heat
pump unit. Contained within the unit enclosure is all
factory wiring, piping, controls, c ompressor,
refrigerant charge (R--22), and special features
required prior to field start--up.
Unit Cabine
t
Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
Fans
Condenser fan will be direct--drive propeller type,
discharging air upward.
AIR--COOLED, SPLIT--SYSTEM HEAT PUMP
213R
1--1/2 TO 5 NOMINAL TONS
Condenser fan motors will be totally enclosed,
1--phase type with class B insulation and permanently
lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically
balanced.
Condenser fan openings will be equipped with steel
wire safety guards.
Compresso
r
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins
mechanically bonded to copper tubes which are then
cleaned, dehydrated, and sealed.
Refrigeration Component
s
Refrigeration circuit components will include
liquid--line shutoff valve with sweat connections,
vapor--line shutoff valve with sweat connections,
system charge of refrigerant, compressor oil,
accumulator, loss of charge switch, and reversing
valve.
Operating Characteristics
The capacity of the unit will meet or exceed _____
Btuh at a suction temperature of _____ _F. The power
consumption at full load will not exceed _____ kW.
Combination of the unit a nd the evaporator or fan coil
unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F wet bulb
and _____ _F dry bulb, and air entering the unit at
_____ _F.
The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
Nominal unit electrical characteristics will be _____ v,
three phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
Refer to section of t his literature identifying
accessories and descriptions for specific features and
available enhancements.
Manufacturerreserves the right todiscontinue, or change atany time, specificationsor designs without notice andwithout incurring obligations.