Bosch Appliances FPA-1000 Smoke Alarm User Manual


 
use these devices on addresses above 127 and other
devices below address 127. All compatible detectors
and modules are addressed using the D5070
Programmer.
Parts Included
Quant. Component
1 FPA‑1000‑V2 main board
1 Enclosure with transformer
1 Enclosure lock and two keys
1
(replacement key: D102)
1 Hardware pack
3 Wiring labels (one each in English, Spanish, and
Portuguese)
2 2.21 kΩ EOL resistors (replacement resistors: EOL‑2.2K, 8
per package)
Tabs with different language versions for LED and key text
Literature (in English, Spanish, and Portuguese)
Installation and Operation Guide
Operating Instruction Sheet
Release Notes
1
Key code stamped on both lock and key
Technical Specifications
Electrical
Power supply (primary)
Current: 120 VAC: 2 A maximum
240 VAC: 1 A maximum
Voltage: 120 VAC, 60 Hz or 240 VAC, 50 Hz
Power supply (secondary)
Current (alarm): Panel < 0.240 A
SLC = 0.63 A maximum
Current (load): Standby: < 1.25 A
Alarm: 4 A Shared maximum
NAC 1 = 2.5 A maximum
NAC 2 = 2.5 A maximum
AUX/FWR = 0.5 A maximum
AUX/RST = 0.5 A maximum
Option bus = 0.5 A maximum
Voltage: 24 VDC
Batteries
Voltage: 2 x 12 VDC in series
Capacities: maximum 40 Ah
in cabinet: 7 Ah to 18 Ah
in additional battery box: 24 Ah
to 40 Ah
Fuses: 15 A blade type
Auxiliary power supply (AUX)
AUX/FWR: 0.5 A at 24 V FWR
Non‑switched, power‑limited, unfiltered,
unsupervised
AUX/RST: 0.5 A at 24 VDC
Switched, power‑limited, filtered,
unsupervised
Environmental
Environment: Indoor, dry
Protection Class: IP 30
Relative Humidity: Up to 95%, non-condensing
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Temperature (storage): +14°F to +131°F (-10°C to +55°C)
Mechanical
Operating Elements
LCD: 4‑line x 20‑character display, backlit
LEDs: Six total: Fire, Gas Alarm, Power,
Supervisory, Silenced, and Trouble
Operation Keys: Drill, Reset, Silence, and Acknowledge
Alphanumeric
Keypad:
12 alphanumeric keys, escape, enter,
and navigation buttons (left, right, up,
down)
Interfaces
PSTN/DACT: 2 lines, RJ45
Ethernet: 1 x RJ45
Peer-to-peer
communication:
Each interconnected panel requires one
of the following:
FPE‑1000‑NE Networking Card
3‑Ethermet
FPE‑1000‑NF Networking Card
1‑Ethernet 2‑Fiber Optic
FPE‑1000‑NW Networking Card
1‑Ethernet 2‑Wired
Network Connections
Ethernet: minimum of CAT 5 cable at a maximum
length of 328 ft (100 m)
Fiber Optics: multi-mode fiber optic cable (62.5 μm/
125 μm fiber size; 1270 nm to 1380 nm
wavelength) with LC connectors at a
maximum length of 6560 ft (2000 m or a
10 db loss, whichever occurs first)
Wired: 12 AWG (2.05 mm) to 26 AWG
(0.41 mm) twisted pair wire (shielded or
unshielded) at a maximum length of
2952 ft (900 m) or CAT 5 cable or better
at a maximum length of 3280 ft
(1000 m)
Wiring
Cable Entries: Triple knock-outs (3/4, 1/2, 1 in)
4 | FPA‑1000 Analog Addressable Fire Panels