Bosch Appliances FPA-1000 Smoke Alarm User Manual


 
interface. Therefore, no software installation is
required. The panel can receive diagnostics from a
Web browser running on a networked PC.
System Overview
Functions
Peer-to-peer Communications
The FPA‑1000 panels (-V2) allow peer-to-peer
networking of up to eight panels in a single group
supporting a system which can include up to 2000
points.
Networked panels act as a single panel – enabling all
events to be displayed on all units. All connected
panels can easily be programmed and controlled via
any connected panel.
Ethernet, fiber optic, or 2-conductor wire inter‑panel
connections can be mixed providing flexibility in
system design.
System Management
A set of interactive Web pages gives you an instant
means to access and record important system
functions. This unique feature enables programming
and diagnostic capabilities while offsite, streamlining
installation and reducing the time required for
servicing the system. And, you can check status and
manage the system from virtually anywhere on the
network.
Communications
The FPA‑1000 panel has a dual phone line PSTN/DACT
circuit and an Ethernet connection featuring Conettix
IP reporting. The panel communicates in Contact ID,
SIA, and Modem IIIa
2
. The panel provides
miscellaneous reporting functions such as dialing
control and transmission supervision, priorities of
report groups, routing to destinations, manual and
auto test reports, and Anti-Replay feature.
For the primary and secondary account, the following
features are programmable:
Two different phone or IP numbers
Different dialing types for PSTN (pulse only,
automatic, or tone only)
Individual PSTN line supervision (audible and visual
trouble signal in the case of a transmission path
failure)
Selectable options for Report Steering Groups
Programmable acknowledge wait time for each IP
reporting Conettix account (10 sec up to 255 sec)
Test report frequency individually programmable for
each account (4, 12, 24 hour, 7 and 28 day intervals,
standard frequency 24 hour)
Applications
The FPA-1000 panels are recommended for a wide
range of commercial and public building applications,
including:
Retail – single building applications
Education – schools and universities
Residential - apartment buildings
Commercial – manufacturing plants, warehouses and
office complexes
Government and Public Service – military bases and
installations
Medical – healthcare facilities
Multi-criteria Detectors
A range of pull stations, modules, accessories and
detectors are available to meet the needs of your
application. These include the new Automatic Fire
Detector 440 Series that incorporate multi-criteria
technology for higher sensitivity, faster detection, and
fewer false alarms.
Gas detection
Integrated gas detection is an important element of
your facility’s fire and life safety strategy. Using
FCC-380 Carbon Monoxide detectors combined with
an addressable monitor module, you can set your
system to alarm for carbon monoxide to meet the
NFPA 720 (2009) requirements for visual and audible
annunciation for this hazardous gas.
Notification Appliance Circuits (NACs)
Two Class A Style Z or Class B Style Y NACs provide up
to 4 A of 24 V power (non-synchronized: 2.5 A per
NAC; synchronized: 2.75 A NAC 1 + NAC 2 in total) to
operate horns, strobes, bells, and other notification
appliances. Each NAC can be programmed to provide
Temporal Code 4, Temporal Code 3, and steady,
pulsing, and synchronized protocol output for
Wheelock, Gentex, and System Sensor notification
appliances.
2
| FPA‑1000 Analog Addressable Fire Panels