Bosch Appliances FPA-1000 Smoke Alarm User Manual


 
On-board Relays
Three programmable on-board relays default to global
alarm (zone 226), global system trouble (zone 227),
and global system supervisory (zone 228). They can be
programmed to activate on a variety of conditions
including gas alarm.
Option Bus
On the Option Bus, the FPA-1000 supports:
up to eight FMR-1000-RCMD Remote Command
Centers and FMR-1000-RA Remote Annunciators in
any combination
up to eight D7030X Series LED Annunciators with
eight LED zones each,
up to eight D7030X Series/D7032 combinations
up to two Octal Relay Modules or Octal Driver
Modules
up to four FPP‑RNAC‑8A‑4C Remote Notification
Appliance Circuit Power Supplies.
The outputs of the Octal Relay Modules or Octal Driver
Modules are fully programmable, and can be activated
by system events. These outputs have the same
programming options as the local relays. Each output
operates independently of the other seven to provide
complete flexibility. Communication with the D7035/B
or D7048/B is supervised.
Power
A transformer working with 120 VAC or 240 VAC is
supplied standard with the control panel. Two backup
batteries with 7 Ah to 18 Ah each fit inside the fire
panel cabinet. A separate battery box can provide
higher capacity. An automated battery calculator sheet
is available online to aid in battery selection and
submittal paperwork.
The FPA-1000 panels provide two auxiliary power
supplies (one FWR and one DC) with 0.5 A at 24 V
each, with switchable AUX/RST. This auxiliary power
can run expansion boards or other low current
auxiliary devices.
For installations requiring battery capacity higher than
40 Ah, a regulated and UL1481 Listed external power
supply can be used. The external power supply
connects through the panel's battery terminals and is
supervised for AC and battery fault by an input module
on the SLC.
The FPP-RNAC-8A-4C Remote NAC Booster adds four
additional Notification Appliance Circuits (NFPA 72,
Class A Style Z or Class B Style Y) to the fire panel or
serves as a power supply for fire protective signaling
systems. This regulated power supply provides up to
8 A of power that is used to recharge batteries and
operate continuous and intermittent alarm loads. This
8 A of power can be distributed through the four NAC
Power Supply circuits that are part of the FPP-
RNAC-8A-4C. The FPP-RNAC-8A-4C is UL Listed for use
in commercial fire alarm applications.
Signaling Line Circuits (SLCs)
The FPA‑1000 Fire Panels communicate with each of
the analog addressable devices located on the SLCs.
The SLCs allow the use of standard non‑twisted,
non‑shielded wiring. Each panel supports two Class B,
Style 4 or one Class A, Style 6 or 7 per SLC.
Certifications and Approvals
Region Certification
USA UL FSZI.S1871: Emergency Alarm System
Control Units (ANSI/UL 2017); UOJZ:
Control Units, System (ANSI/UL 864)
CSFM 7165-1615:0229
FDNY-
CoA
#6101
Installation/Configuration Notes
Mounting Considerations
The cabinet can be either semi-flush (requires optional
FPM‑1000‑SFMK Semi-flush Mounting Kit) or surface
mounted.
Depending on the configuration and the battery
selection, the FPA‑1000 can be quite heavy. When
attaching the enclosure to a surface, use mounting
hardware (not supplied) capable of supporting this
weight, and reinforce the wall as necessary.
Wiring Considerations
The length of wire allowed between the control panel
and the last device on a wiring run depends on the
current drawn on that wiring run. Reducing the
number of devices on a wiring run allows the
individual runs to be longer.
If not otherwise specified, use wire gauge 12 AWG to
18 AWG (3.3 mm
2
to 0.8 mm
2
).
Notice
Shared cable is not recommended for the Option
Bus, addressable‑points bus, telephone, or NAC
wiring. Do not run wiring for NAC, Option Bus,
and SLC in the same conduit. Avoid shielded or
twisted-pair wire except for network connections
and special applications where a reduced length
of wiring (roughly 50%) is acceptable for
tolerating a harsh electrical environment.
Point Capacity/Configuration
Each FPA-1000-V2 panel supports up to 508
addresses, 254 per loop. For addresses above 127 on
each loop, only the FAA‑325‑B6S Sounder base,
FAP‑325‑V2F Smoke Detector, FLM‑325-I4‑A,
FLM‑325‑I4‑AI, and FLM-325-IM Contact Monitors,
FLM‑325‑NA4 and FLM‑325‑NAI4 Supervised Output
Modules, FLM-325-2R4-2A and FLM‑325‑2R4‑2AI 2 A
Dual Relay Modules, and FLM‑325‑2R4‑8A and
FLM‑325‑2R4‑8AI 8 A Dual Relay Modules can be used.
For systems requiring more than 127 points per loop,
3
| FPA‑1000 Analog Addressable Fire Panels