The controls must be installed in accordance with UL Standards
UL681 and UL609 for all grades of service.
1. Report Programming:
Burglar Zone Reports must be programmed for those zones
used.
• Low Battery Report (Program Address 3336) must be
programmed.
AC Failure Report (Program Address 3338) must be
programmed.
Open Report (Program Address 3331) must be programmed.
Close Report (Program Address 3332) must be programmed.
24-Hour Check-In Reports (Program Addresses 3340 and 3347)
must be programmed.
2. General Control Programming:
The control must not be programmed for auto disarm.
Must be programmed for no swinger shunts and closing ringback.
(Program Address 0000 data digit 2, enter 0, 1, or 2).
Program Address 2732 must be programmed as: Data Digit 1=
0, Data Digit 2= 0.
3. Zone Function Programming:
The Burglar alarm signal (whether pulsed or steady) must be
different from the Fire alarm signal.
4. Alarm Output Programming:
Program Address 2734 must be programmed as: Data Digit 1=
6, Data Digit 2 = 3.
Program Address 2737 must be programmed as: Data Digit 1=
8.
11.4.1Local Burglary Alarm
A.Grade A Installations using Digital Alarm Communicator
Transmitter with local bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
An Ademco Model AB-12 bell/housing (see section 11.6).
1. Timer Programming:
Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
Entry, Exit Delay Times (Program Addresses 4028-4029) must
be programmed for not longer than 60 seconds.
11.4.2Police Station Connection
Follow General System Requirements as listed in 11.4.
Required Accessories:
The control must be in the Detection Systems’ model AE3CC
enclosure with a cover actuated tamper switch installed.
An DS7416i (or DataTAC) interface module.
The DS7416i module and antenna should be mounted within
the protected area.
The Detection Systems’ model DS7481 Phone Line Monitor.
1.Timer Programming:
Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
B.Grade A Installations Using Digital Alarm Communicator
Transmitter With Local Bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
The Ademco Model AB-12 bell/housing (see section 11.6).
1.Timer Programming:
Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
11.4.3Central Station Burglary Alarm and Proprietary
A.Central Station Burglary Grades AA and A and Proprietary
Grade AA Installations Using an DS7416i Interface Module
Follow General System Requirements as listed in 11.4.
Required Accessories:
The control must be in the Detection Systems’ model AE3CC
enclosure with a cover actuated tamper switch installed.
An DS7416i (or DataTAC) interface module.
The DS7416i module and antenna should be mounted within
the protected area.
The Detection Systems’ model DS7481 Phone Line Monitor.
The Ademco Model AB-12 bell/housing (see section 11.6).
1.Timer Programming:
Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
B.Grade B Installations Using Digital Alarm Communicator
Transmitter With Local Bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
The control must be in the Detection Systems’ model AE3CC
enclosure with a cover actuated tamper switch installed.
The Ademco Model AB-12 bell/housing (see section 11.6).
1.Timer Programming:
Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
C.Central Station Burglary Grade C and Proprietary Grade A
Installations Using Digital Alarm Communicator Transmitter only
Follow General System Requirements as listed in 11.4.
Required Accessories:
The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
1.Timer Programming:
Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
Burglary Alarm -
11.4 General System Requirements
Applies to the following grades only:
Local Burglary Grade A using Digital Alarm Communicator
Transmitter (DACT)
Police Station Grades AA and A using DACT and DS7416i
Communications module.
Grade A using DACT and local Bell.
Central Station Grades AA and A using DACT and DS7416i
Communications module.
Grade B using DACT and local bell.
Grade C using Digital Alarm Communicator
Transmitter only.
Alarm -
Connection -