Bosch Appliances DS7400XIV4-EXP Home Security System User Manual


 
DS7400XiV4-EXP | User Guide | 10.0 Testing Your System EN | 29
Bosch Security Systems | 6/05 | 4998154961B
10.4 Fire Walk Test
This test confirms that smoke detectors report alarms to the keypads. The Fire Walk Test tests all fire zones,
including verified fire and waterflow.
This test requires you to manually alarm each zone.
If programmed, a Fire Walt Test report is sent to the central station at the start of a Fire Walk Test. Fire alarm
reports are not sent to the central station during the Fire Walk Test. A Fire Walk Test restoral is sent upon
completion of the Fire Walk Test.
The Fire Walk Test runs for 20 minutes once it is started. The test time is extended to 20 minutes every time you
test another zone.
When you test a fire zone, any output programmed to follow that zone is activated for 5 seconds.
Table 28: Fire Walk Test
Type of Test Command Sequence What Happens What To Do
Fire Walk Test [PIN][#][9][1]
“Fire Test” is displayed followed by the number
of any zones that are untested. *
The LEDs of any untested zones flash. **
“Fire Testing” is displayed followed by the
number of the zone currently being tested. *
The LED for the zone currently being tested
turns on steady. **
As each zone is tested, the “Fire Test” message
appears followed by the remaining untested
zones. *
As each zone is tested, its LED turns off. **
Test each zone as
instructed by your
installing company.
Exit the Fire Walk Test
using [PIN][#].
* Text keypad only
** LED keypad only
A Fire Walk Test prevents the system from sending any Fire Reports during the test.