Pre-installation checklist
Table 1 – Nozzle capacities at various pressures
Combustion air supply
The burner requires combustion air and ventilation air for
reliable operation. Assure that the building and/or com-
bustion air openings comply with National Fire Protection
Standard for Oil-Burning Equipment, NFPA 31. For appli-
ance/burner units in confined spaces, the room must have
an air opening near the top of the room plus one near the
floor, each with a free area at least one square inch per
1,000 Btu/hr input of all fuel burning equipment in the
room. For other conditions, refer to NFPA 31 (CSA B1139-
M91 in Canada).
If there is a risk of the space being under negative pressure
or of exhaust fans or other devices depleting available air
for combustion and ventilation, the appliance/burner
should be installed in an isolated room provided with out-
side combustion air.
Clearances
With the burner installed in the appliance, there must be
adequate space in front of and on the sides of the burner to
allow access and operation. Verify that the clearance di-
mensions comply with all local codes and with the appli-
ance manufacturer's recommendations.
Fuel supply
The fuel supply piping and tank must provide #1 or #2
fuel oil at pressure or vacuum conditions suitable for the
fuel unit (oil pump) on the burner. Refer to fuel unit litera-
ture in the literature envelope in the burner carton to verify
allowable suction pressure.
When fuel supply is level with or higher than burner
fuel unit —
When the fuel unit is not required to lift the oil, the instal-
lation is usually suitable for either a one-pipe or two-pipe
oil system. The oil pressure at the inlet of the fuel unit must
not exceed 3 psig.
The fuel unit is shipped with the by-pass plug installed.
Leave the by-pass plug installed for all low/high firing
burners, regardless whether one-pipe (with by-pass loop)
or two-pipe. See Figure 8 for installation of the by-pass
loop required for one-pipe fuel supply installations. See
Figure 9 for connections to the fuel unit for two-pipe fuel
supply installations.
When fuel supply is below the burner fuel unit —
Use a two-pipe oil system when the fuel unit must lift the
oil more than 8 feet if burner is equipped with a B fuel unit
— or more than 2 feet if burner is equipped with an H fuel
unit. The return line provided by the two-pipe system is
needed to purge the air from the fuel lines and minimize
the likelihood of air-related problems during operation.
Vent system
The flue gas venting system must be in good condition
and must comply with all applicable codes.
Electrical supply
Verify that the power connections available are correct for
the burner. All power must be supplied through fused dis-
connect switches.
Verify burner components —
Burner box, Model CF2300A
Air tube assembly (selected per following)
Mounting flange kit
Pedestal mounting assembly kit (recommended)
Oil nozzle, per Table 1 — Use only 45° to 70° solid pat-
tern nozzles unless otherwise shown by appliance manu-
facturer.
Find the required firing rate in the 300 psig column (high
fire rate).
Select the corresponding nozzle from column 1 (Rated
gph @ 100 psig).
Rated
gph @
100 psig
Pressure - pounds per square inch
125 150 175 250 275 300
4.50 5.04 5.51 5.95 7.11 7.46 7.79
5.00 5.59 6.12 6.61 7.91 8.29 8.66
5.50 6.15 6.74 7.28 8.70 9.12 9.53
6.00 6.71 7.35 7.94 9.49 9.95 10.39
6.50 7.27 7.96 8.60 10.28 10.78 11.26
7.00 7.83 8.57 9.26 11.07 11.61 12.12
7.50 8.39 9.19 9.92 11.86 12.44 12.99
8.00 8.94 9.80 10.58 12.65 13.27 13.86
9.00 10.06 11.02 11.91 14.23 14.92 15.59
10.00 11.18 12.25 13.23 15.81 16.58 17.32
11.00 12.30 13.47 14.55 17.39 18.24 19.05
12.00 13.42 14.70 15.87 18.97 19.90 20.78