Beckett CF3500A Burner User Manual


 
Weil McLain
88
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
488R CF1400 BCF205 CF66KD 6.90 4.00x70B 1 30 120 125 300 51629 4.00"
488 CF1400 BCF205 CF66KD 7.00 4.00x70B 1 30 120 125 300 51629 4.00"
588 CF1400 BCF205 CF66KD 9.40 5.50x70B 3 40 120 125 300 51629 4.00"
688 CF2300 BCF304 CF66KG 11.80 6.50x60B 2 20 30 125 300 51630 4.00"
788 CF2300A BCF304 CF66KG 14.20 8.00x60B 3 20 30 125 300 51630 4.00"
888 CF2300A BCF304 CF66KG 16.60 9.50x60B 5 30 60 125 300 51630 4.00"
988R CF2300A BCF304 CF66KG 17.20 10.00x60B 8-1/2 38 95 125 300 51630 4.00"
988 CF2300A BCF304 CF66KS 18.20 11.00x45P 1-1/2 38 63 150 275 51630 4.00"
1088R CF2300A BCF304 CF66KS 19.90 12.00x45P 2 40 65 150 275 51630 4.00"
1088 CF2500 BCF1801 CF66KP 21.50 6.00x60B (2) 2 18 40 300 300 51630 4.00"
1188 CF2500 BCF1801 CF66KP 23.50 6.50x60B (2) 4 20 40 300 300 51630 4.00"
1288 CF3500 BCF1301 CF80KM 26.00 7.50x60B (2) 7 24 60 300 300 51630 4.50"
1388 CF3500 BCF1301 CF80KM 28.50 8.50x60B (2) 7 26 70 300 300 51630 4.50"
1488 CF3500 BCF1301 CF114KR 29.90 9.00x60B (2) 7 50 100 300 300 51631 5.375"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 32