Beckett CF3500A Burner User Manual


 
Buderus
G215
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
3 AFG B2007 AFG50ML 1.10 0.90x45ES 0 8 1 N/A 170 51311 3.50"
4 AFG B2007 AFG50ML 1.40 1.10x45ES 2 8 2 N/A 175 51311 3.50"
5 CF375 BCF3907 CF56KY 1.75 1.35x45ES 2 5 1 N/A 170 51311 3.50"
6 CF375 BCF3907 CF56KZ 2.10 1.75x45ES 1 7 2 N/A 140 51311 3.50"
7 CF375 BCF3907 CF56KZ 2.50 2.00x45P 1 9 3 N/A 150 51311 3.50"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Buderus
G315
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
5 CF500 BCF809 CF80KK 3.00 2.50x45P 3 7 0 N/A 140 51311 4.75"
6 CF800 BCF403 CF80KH 3.85 3.25x45P 1 7 0 N/A 140 51311 4.75"
7 CF800 BCF403 CF80KH 4.70 4.00x45P 2 10 0 N/A 140 51311 4.50"
8 CF1400 BCF205 CF66KD 5.50 3.25x45P 1 20 35 150 275 51312 4.50"
9 CF1400 BCF205 CF66KD 6.40 3.75x45P 3 25 40 150 275 51312 4.50"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Buderus
G515
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
7 CF1400 BCF205 CF102KD 6.90 4.00x60P 5 20 30 150 300 51312 6.00"
8 CF1400 BCF205 CF102KD 8.40 5.00x60P 9 30 43 150 275 51312 6.00"
9 CF2300A BCF304 CF102KG 10.00 5.50x45P 0 20 33 150 300 51312 6.00"
10 CF2300A BCF304 CF102KG 11.60 6.50x45P 2 25 40 150 300 51312 6.00"
11 CF2300A BCF304 CF102KG 13.00 7.50x45P 6 25 40 150 300 51312 6.00"
12 CF2300A BCF304 CF102KG 14.60 8.50x45P 8-1/2 30 70 150 300 51312 6.00"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 2