Beckett CF3500A Burner User Manual


 
Weil McLain
80
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
380 CF500 BCF809 CF60KK 2.40 2.00x60B (D) 1-1/2 4 0 N/A 140 51311 3.00"
480 CF500 BCF809 CF60KK 3.40 2.75x45PLP 4 10 3 N/A 150 51311 3.00"
580 CF800 BCF403 CF60KHS 4.45 3.75x30P 2 7 0 N/A 150 51311 3.00"
680 CF800 BCF403 CF60KHS 5.50 4.50x45P 4 10 3 N/A 150 51311 3.00"
780 CF1400 BCF205 CF66KD 6.50 3.75x45P 3 20 45 150 300 51629 4.00"
880 CF1400 BCF205 CF66KD 7.50 4.50x45P 4 25 45 150 275 51629 4.00"
980 CF1400 BCF205 CF66KD 8.50 5.00x45P 5 25 60 150 300 51629 4.00"
1080 CF1400 BCF205 CF66KE 9.60 5.50x45P 3 30 60 150 300 51629 4.00"
1180 CF2300A BCF304 CF66KG 10.60 6.00x45P 0 15 30 150 300 51630 4.00"
1280 CF2300A BCF304 CF66KG 11.60 7.00x45P 1/2 30 60 150 280 51630 4.00"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 31