Beckett CF3500A Burner User Manual


 
Crown Boiler
CT
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
CT6 SMG B1403 SMG45NR 1.65 1.35x45ES 0 7 1 N/A 150 51311 1.75"
CT6 CF375 BCF3907 CF56KY 1.65 1.35x60ES 1 6 0 N/A 150 51311 1.75"
CT7 CF500 BCF809 CF60KK 2.00 1.75x60ES 1 3-1/2 0 N/A 140 51311 2.25"
CT8 CF500 BCF809 CF60KK 2.50 2.00x45B 2 4-1/2 0 N/A 140 51311 2.25"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Crown Boiler
F
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
F4 CF800 BCF403 CF80KHS 3.00 2.50x60B 0 4 0 N/A 140 51311 7.00"
F5 CF800 BCF403 CF80KHS 4.00 3.25x45P 1 5 0 N/A 140 51311 7.00"
F6 CF800 BCF403 CF80KHS 5.00 4.00x45P 3 7 0 N/A 140 51311 7.00"
F7 CF1400 BCF205 CF102KD 6.00 3.50x45P 2 25 38 125 275 51312 7.00"
F8 CF1400 BCF205 CF102KD 7.50 4.50x45P 4 35 60 125 275 51312 7.00"
F9 CF2300A BCF304 CF102KG 9.00 5.00x45P 0 20 33 150 275 51630 7.00"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Flange requires an additional adapter plate.
Crown Boiler
FW
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
FW4 CF500 BCF809 CF80KK 3.00 2.50x60B 2-1/2 4-1/2 0 N/A 140 51311 4.75"
FW5 CF800 BCF403 CF80KHS 4.00 3.25x45P 1 5 0 N/A 140 51311 4.75"
FW6 CF800 BCF403 CF80KHS 5.00 4.00x45P 3 7 0 N/A 140 51311 4.75"
FW7 CF1400 BCF205 CF102KE 6.00 3.50x45P 2 25 38 125 275 51312 4.75"
FW8 CF1400 BCF205 CF102KE 7.50 4.50x45B 4 35 60 125 275 51312 4.75"
FW9 CF2300A BCF304 CF102KG 9.00 5.50x45P 0 20 33 150 275 51313 4.75"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Flange requires an additional adapter plate.
Page 12