Beckett CF2500A Burner User Manual


 
Weil McLain
88-2
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
488 CF1400 BCF205 CF66KD 7.00 04.00x70B(D ) 4 39 54 150 300 0 4.00"
588 CF2300A BCF304 CF66KG 9.40 05.50x60P 0 34 42 150 300 0 4.00"
688 CF2300A BCF304 CF66KG 11.80 07.00x60B(D ) 3 41 51 150 300 0 4.00"
788 CF2300A BCF304 CF66KG 14.20 08.50x60B(D ) 6 43 54 150 280 0 4.00"
888 CF2500A BCF3001 CF66KP 16.60 05.00x45PLP 2 24 50 300 300 0 4.00
988 CF2500A BCF3001 CF66KP 18.80 05.50x60P(H ) 4.00 27 52 300 0 4.00"
1088 CF2500 BCF1801 CF66KP 21.50 06.50x60B(D ) 8 28 54 300 0 4.00"
1188 CF2500 BCF1801 CF66KP 23.50 07.00x45B(D ) 8 29 44 300 0 4.00"
1288 CF3500A BCF1301 CF80KM 26.00 07.50x45B(D ) 3 31 63 300 0 4.50"
1388 CF3500A BCF1301 CF80KM 28.50 08.50x45B(D ) 6 33 98 300 0 4.50"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
0.5 DEGREE PITCH
Page 33