Beckett CF2500A Burner User Manual


 
Weil McLain
76
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
476 CF500 BCF809 CF60KK 2.35 2.00x45B 1 4 0 N/A 140 51311 2.875"
576 CF500 BCF809 CF60KK 2.95 2.50x45B 3 5 0 N/A 140 51311 2.875"
676 CF500 BCF809 CF60KK 3.60 3.00x45B 5 10 4 N/A 140 51311 2.875"
776 CF500 BCF809 CF60KK 4.25 3.50x45B 6 10 5 N/A 140 51311 2.875"
876 CF800 BCF403 CF60KH 4.90 4.00x45B 1 8 0 N/A 140 51311 2.875"
976 CF800 BCF403 CF60KH 5.50 4.50x45B 3 10 0 N/A 140 51311 2.875"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Weil McLain
78
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
378 CF500 BCF809 CF60KK 2.40 2.00x45B 1-1/2 6 0 N/A 140 51311 3.00"
478 CF500 BCF809 CF60KK 3.40 2.75x45P 4 10 2 N/A 150 51311 3.00"
578 CF800 BCF403 CF60KHS 4.45 3.75x30P 2 7 0 N/A 150 51311 3.00"
678 CF800 BCF403 CF60KHS 5.50 4.50x45P 4 10 3 N/A 150 51311 3.00"
778 CF1400 BCF205 CF66KD 6.50 3.75x45P 3 20 45 150 300 51629 4.00"
878 CF1400 BCF205 CF66KD 7.50 4.50x45P 4 25 45 150 275 51629 4.00"
978 CF1400 BCF205 CF66KD 8.50 5.00x45P 5 25 60 150 300 51629 4.00"
1078 CF1400 BCF205 CF66KE 9.60 5.50x45B 3 30 60 150 300 51629 4.00"
1178 CF2300A BCF304 CF66KG 10.60 6.00x45P 0 15 30 150 300 51630 4.00"
1278 CF2300A BCF304 CF66KG 11.60 7.00x45P 1/2 20 50 150 280 51630 4.00"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 30