Beckett CF2300A Burner User Manual


 
Burnham Corporation
V11
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
V1104 CF1400 BCF205 CF66KD 5.80 3.50x45P 0 25 50 150 300 51629 4.12"
V1105 CF1400 BCF205 CF66KE 7.40 4.50x45P 0 30 50 150 300 51629 4.12"
V1106 CF1400 BCF205 CF66KE 9.20 5.50x45P 2 30 60 150 300 51629 4.12"
V1107 CF2300A BCF304 CF66KG 11.00 6.50x45P 2 30 60 150 300 51630 4.00"
V1108 CF2300A BCF304 CF66KG 13.00 7.50x45P 4 35 60 150 300 51630 4.12"
V1109 CF2300A BCF304 CF66KG 14.80 8.50x45P 4 35 75 150 300 51630 4.12"
V1110 CF2300A BCF304 CF66KS 16.60 9.50x45P 4 30 55 150 300 51630 4.12"
V1111 CF2300A BCF304 CF66KS 18.40 10.50x45P 6 40 60 150 300 51630 4.12"
V1112 CF2500A BCF1801 CF66KP 20.00 5.50x45P (2) 4 20 45 300 300 51630 4.12"
V1113 CF2500A BCF1801 CF66KP 21.50 6.00x45P (2) 5 22 55 300 300 51630 4.12"
V1114 CF3500 BCF1301 CF80KM 23.50 6.50x45P (2) 2 25 80 300 300 51630 4.12"
V1115 CF3500A BCF1301 CF80KM 25.50 7.00x45P (2) 3 30 90 300 300 51630 4.12"
V1116 CF3500A BCF1301 CF114KR 27.00 7.50x45P (2) 6 32 85 300 300 51631 5.50"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.