19
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
19-3 CF500 BCF809 CF80KK 2.60 1.75x60ES 2 4 0 N/A 180 51628 1.75"
19-4 CF500 BCF809 CF80KK 3.60 3.00x45B 5 8 0 N/A 140 51628 1.75"
19-5 CF800 BCF403 CF80KH 4.60 4.00x60PLP 3 10 5 N/A 140 51628 3.875"
19-6 CF800 BCF403 CF80KH 5.60 4.50x60PLP 4 10 8 N/A 140 51628 3.875"
19-7 CF1400 BCF205 CF66KD 6.50 4.00x45PLP 3-1/2 30 60 125 275 51629 3.875"
19-8 CF1400 BCF205 CF66KE 7.50 4.50x45PLP 2 30 50 125 275 51629 3.875"
19-9 CF1400 BCF205 CF66KE 8.50 5.00x45PLP 3 35 60 125 300 51629 3.875"
19-10 CF1400 BCF205 CF66KE 9.50 5.50x45PLP 4 40 70 125 300 51629 3.875"
19-11 CF1400 BCF205 CF66KE 10.40 6.00x45PLP 5-1/2 40 80 125 300 51629 3.875"
19-12 CF2300A BCF304 CF66KG 11.40 6.50x45PLP 1 16 30 125 300 51630 3.875"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Smith Cast Iron Boilers
19A
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
19A-3 CF500 BCF809 CF80KK 2.60 1.75x60ES 2 4 0 N/A 180 51628 1.75"
19A-4 CF500 BCF809 CF80KK 3.60 3.00x45B 5 8 0 N/A 140 51628 1.75"
19A-5 CF800 BCF403 CF60KH 5.00 4.00x45B 2 10 4 N/A 150 51628 4.00"
19A-6 CF1400 BCF205 CF66KD 6.40 4.00x45P 2-1/2 28 40 150 250 51629 4.00"
19A-7 CF1400 BCF205 CF66KD 7.80 4.50x45P 3-1/2 35 60 150 300 51629 4.00"
19A-8 CF2300A BCF304 CF66KF 9.30 5.50x60B ( D) 3 15 43 125 275 51630 3.50"
19A-9 CF2300A BCF304 CF66KG 10.70 6.50x45P 0 23 28 175 275 51630 4.00"
19A-10 CF2300A BCF304 CF66KG 12.10 7.00x45P 0 25 33 175 275 51630 4.00"
19A-11 CF2500 BCF1801 CF102KP 13.50 5.00x45B 0 18 25 300 300 51630 4.50"
19A-12 CF2500 BCF1801 CF102KP 15.00 5.50x45P 0 20 30 300 300 51630 4.50"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.