Beckett CF2300A Burner User Manual


 
Burnham Corporation
E
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
E20 CF800 BCF403 CF80KJ 6.00 5.00x60SS 2 10 5 N/A 140 51628 5.50"
E20 CF1400 BCF205 CF66KE 6.00 3.50x60SS 1/2 20 40 125 300 51629 5.50"
E30 CF1400 BCF205 CF66KE 9.00 5.00x60SS 3 30 60 125 300 51629 5.50"
E40 CF2300A BCF304 CF66KG 12.00 7.00x60SS 1 30 40 125 300 51630 5.50"
E50 CF2300A BCF304 CF66KG 15.00 9.00x60SS 4 25 30 125 300 51630 5.50"
E60 CF2300A BCF304 CF66KG 18.00 11.00x60SS 6 35 90 125 300 51630 5.50"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Burnham Corporation
FD
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
FD-9 CF500 BCF809 CF60KK 2.75 2.00x45P 2 4 0 N/A 150 51311 3.375"
FD-10 CF500 BCF809 CF60KK 3.00 2.50x45P 2 4 0 N/A 150 51311 3.375"
FD-12 CF800 BCF403 CF60KH 4.00 3.25x45P 1-1/2 5-1/2 0 N/A 150 51311 3.375"
FD-14 CF800 BCF403 CF60KH 4.50 3.75x45P 2 7 0 N/A 150 51311 3.375"
FD-15 CF800 BCF403 CF60KH 5.00 4.00x45P 2 8 0 N/A 150 51311 3.375"
FD-19 CF800 BCF403 CF60KH 6.00 4.50x60B 4 10 2 N/A 150 51628 3.375"
FD-24 CF1400 BCF205 CF66KD 7.50 4.50x45P 3 30 55 150 300 51629 3.375"
FD-30 CF1400 BCF205 CF66KE 9.50 5.50x45P 1-1/2 30 75 150 300 51629 3.375"
FD-38 CF2300A BCF304 CF66KG 12.00 7.00x45P 1 25 45 150 300 51313 3.375"
FD-45 CF2300A BCF304 CF66KG 13.80 8.00x45P 1-1/2 25 60 150 300 51313 3.375"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Page 4