TROUBLESHOOTING
FIGURE 8
FAN BLADE SETTING
MIS-1724
TABLE 1
FAN BLADE DIMENSION
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each
side of unit, and remove grilles.
3. Unwire condenser fan motor.
4. Remove the bolts and nuts holding the condenser fan
motor bracket to the fan shroud.
5. Slide the condenser fan motor and bracket to the rear
of the condenser section.
6. Remove screws holding fan shroud to condenser and
bottom support plate.
7. Slide fan shroud out the left side of the unit.
8. Reverse steps to install.
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of
refrigerant listed on the serial plate. AHRI capacity and
efficiency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures
for the units. Since many installation specific situations
can affect the pressure readings, this information should
only be used by certified technicians as a guide for
evaluating proper system performance. They shall not
be used to adjust charge. If charge is in doubt, reclaim,
evacuate and recharge the unit to the serial plate charge.
ledoM
noisnemiD
A
1VR3W
1VL3W
"52.1
1VR5W
1VL5W
"57.1
1VR6W
1VL6W
"57.1
FAN BLADE SETTING DIMENSIONS
Shown in Figure 8 is the correct fan blade setting for
proper air delivery across the outdoor coil. Refer to
Table 1 for unit specific dimension.
Any service work requiring removal or adjustment in
the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.