UNIT COMPONENTS Magic-Pak: HW/HWC
SRM-HW/HWC 2/99
Flame Carryover Problems
During ignition, the flame must travel uninterrupted from one burner to the
rest of the burners.
Causes:
Carryover “wing” on burner is plugged with insects or debris
Improper gap setting on wings
Incorrect gas pressure
The burner wing has a specified gap (typically 0.025" +/– .002"), which
must carry gas and a small flame to allow flame carryover from one
burner to the next. Check the gap settings on all burners.
Orifice
Smooth end slips
into burner
Gas Entry
Threads
into manifold
Flame Exit
.025 gap (+/ .002 )
for flame carryover
""
FIGURE 5-11 Inshot Burners
FIGURE 5-12 Burner Wing Gap
Armstrong P/N: 41948-001
Gap = .025" +/– .002"