Aprilaire 8600 Thermostat User Manual


 
8
SETUP & TESTING
SYSTEM TEST MENU
The system test menu is used to test a system after installation. The outputs of the thermostat can be manually
activated to test their function. The instructions below show how to enter the test mode and turn outputs on and off.
Test Number System test
60 Heating equipment test
61 Cooling equipment test
62 Auxiliary equipment test (HP only)
63 Fan equipment test
The test number is displayed on the upper left, and the
output state is displayed in the message center.
Press
to turn on the output (01). For multi stage
output, press
again to turn on the 2nd stage (02).
Press
to turn off all the output (00).
Press [BACK] or [NEXT] to change to the next test
step.
When the last step (63) is done, press [NEXT]. The
message “installer test complete“ will display.
All minimum on and off timers will be reset after
returning from system test mode.
Note: Second stage will only be displayed when the
thermostat is set to multi-stage mode.
TEST NUMBER MODEL
(SW1 SETTING)
FLASHES
IF 24VAC
IS NOT
PRESENT
STAGE
OUTPUT
STATE
HOW TO ENTER THE SYSTEM TEST MENU:
Press [MODE] to set system to off.
Press and hold [FAN] and [MODE] for three seconds
to enter system test mode.
The screen of the first test step #60 is displayed:
61000729A 8600 Tstat Install.indd 8 10/8/10 10:32:43 AM