11NetShelter CX Enclosure: Installation and Customization
Vertical Mounting Flanges
Vertical mounting flanges come factory-installed on the enclosure in the
proper position for use with rack-mountable equipment having a depth
of 800 mm (31.5 in). The front mounting flanges are adjustable towards
the rear of the enclosure to accommodate different rails or equipment
with other depths.The rear mounting flanges are adjustable towards the
front. The flanges can be adjusted to be as close as 120 mm (4.7 in) or
as far as 880 mm (34.6 in) apart in 40 mm (1.5 in) increments.
Note: If the front accessory channel is removed from the enclosure, the
front rails can be adjusted forward 8 cm (3.14 in).
A common application for the enclosure is to move the flanges to a
depth of 476 mm (18.75 in) to accommodate networking and
telecommunications equipment.
Adjusting the vertical mounting flanges on the side braces
Perform this procedure without any equipment installed on the
mounting flanges.
1. Use a Phillips screwdriver (not provided) to
remove the screws in the vertical mounting
flange.
2. Move the pre-installed caged nut to the desired
location, then reposition the vertical mounting
flange to this position and install the screws.
ns1551a
ns1552a
ns1553a