Aarrow Fires SF 50 Stove User Manual


 
10
6. THE AIR SYSTEM
Flue Outlet/Hot Plate only for Sf
The flue outlet is packed together with the firebrick lining and multi-purpose tool, inside the appliance. The hot
plate comes fitted on the top of the fire.
To fit flue outlet:
Select the desired position (top or rear outlet)
Smear a very thin layer of suitable sealant or fine adhesive fire cement around the edge of the flue cut-out in
the appliance
Fit outlet and lock into place by rotating anti-clockwise
Similarly fit the hot plate to the unused position
Clean off surplus sealant
Air Inlet Controls
Stratford Multifuel Sf & Si fires have two air inlets.
1. The air wash system (so called because its pre-heated high speed air washes across the inner face of the door
glass, keeping it clear), which provides over draught, and
2. The primary air inlet providing under draught to the base of the fire chamber.
Primary Air
On all Multifuel units primary air enters the appliance through the gap between the body and the ash pit door.
The width of the gap is controlled by rotating the knob (if hot, with the operating tool) anti-clockwise to increase
the air inlet, clockwise to reduce the air inlet, or to seal the ash door completely.
On units fitted with a thermostat, partial opening of the ash door will over-ride and negate the thermostatic
control.
Note: Opening or part opening of the ash door is controlled by the "interlock" device located in the front of
the unit (refer to INTERLOCK section on page 9)
Thermostats
Stratford Sf
Integral Boiler units have a thermostatically controlled rear air inlet. The damper plate at the back
of the appliance regulates the amount of under draught entering, depending on the setting of the thermostat
control knob (located at the bottom rear of the right hand side of the unit) and the temperature of the water
transmitted through the sensor phial in the water jacket.
Stratford Si
units have a thermostatically controlled side air inlet. The damper plate at the side of the appliance
regulates the amount of under draught entering, depending on the setting of the thermostat control knob (located
at the top of the left hand side of the unit) and the temperature of the water/air transmitted through the sensor
phial in the water/air jacket.
Stratford Sf & Si
: with the ash door fully shut, the settings range from 0 (fully anti-clockwise) a shut-off setting
at which the damper will shut off the under draught completely, causing the fire to die down and in time go out,
to 8 (fully clockwise) the highest setting at which the appliance will burn fiercely and produce very high outputs.
Note: The area around the thermostat, both inside at the back of the firebox and externally, must be cleared
of ash and other debris regularly.
For setting instructions refer to "Checking Thermostat" in the installation instructions.
On units fitted with a thermostat, partial opening of the ash door will over-ride and negate the thermostatic
control.
Air Wash
The air wash has an internal sliding plate with slots, housed in a cover plate, and is located above the fire door.
Sliding the control shaft to the right as far as will go achieves the fully open position. Sliding it the left will shut
off the air inlet slots. The operating tool should be used to tap the control shaft to the desire setting. Even when
all the slots are completely shut a "bleed" of secondary air will be maintained ensuring that inflammable gases
are burnt off.