3
78-8126-0432-6-A
1.0 Kit Contents:
1.1 Kit Contents are as follows:
3 ..............Cold Shrink 5467A QS-III Silicone Splice Bodies
6 ..............Tubes, P55/R Red Compound
3 ..............Metallic Shield Sleeves
6 ..............Constant Force Spring Shield Connectors (1.31" I.D.)
2 ..............Constant Force Spring Shield Connectors (1.54" I.D.)
1 ..............Armor to Armor Continuity Braid
2 ..............Cold Shrink Jacket Tubes
1 ..............3M
™
CC-2 Cable Preparation Kit
1 ..............Roll, Scotch
™
33+ Vinyl Electrical Tape (3/4" x 66')
5 ..............Rolls, Scotch
™
Super 88 Vinyl Electrical Tape (1 1/2" x 44')
4 ..............Rolls, Scotch-Seal
™
2229 Mastic Tape (3 3/4" x 10')
1 ..............Roll, Scotch
™
24 Electrical Shielding Tape (1" x 15')
1 ..............Roll, Scotch
™
2228 Rubber Mastic Tape (2" x 10')
6 ..............Rolls, Armorcast
™
Structural Material (4" x 15')
6 ..............Cold Shrink Adapter Tubes (3 white core and 3 red core)
1 ..............Instruction Sheet
6 ..............Copper Foil Tape (1/2" x 10")
12 ............Gloves
2.0 Prepare Cable
2.1 Prepare the cable according to your company's
standard procedures. Allow cable ends to overlap as
much as 10" (254 mm).
Remove 33" (838 mm) of cable jacket, plus half of
the overlap from Cable X.
Remove 25" (635 mm) of cable jacket, plus half of
the overlap from Cable Y.
Keep a 22" (559 mm) piece of cable jacket removed
from Cable X and a 14" (356 mm) piece of jacket
from Cable Y for use later in these instructions.
2.2 If cable is armored, remove cable armor leaving
1 1/2" (37 mm) armor exposed beyond jacket end.
Remove cable binder , if present, at the end of the
jacket or armor and discard.
Fold cable fillers and ground wire(s) back over
cable jacket end. Do not cut off.
Temporarily hold the fillers and ground wire(s) back
by banding them to the cable jacket using Scotch
™
33+ vinyl tape.
Cable Y
25" (635 mm)
Cable X
33" (838 mm)
remove
binder
fold fillers back
DO NOT CUT OFF
1 1/2"
(37 mm)