3M 78-8126-0432-6-A Air Conditioner User Manual


 
Cold Shrink QS-III
Three-Conductor Splice Kit for use on
Armor and Non-Armor Cables
Instructions
IEEE Std. 404
35 kV Class
250 kV BIL
* Splices (including size transitions) can be made to smaller or larger conductors, provided
both cables are within the Insulation O.D. Range and the connector meets the dimensional
requirements shown below.
Connector Dimensional Requirements
Minimum Maximum
inches (mm) inches (mm)
Outside Diameter 0.51" (13,0 mm) 1.70" (43,2 mm)
Length
Aluminum (Al/Cu) ------ 6.00" (152 mm)
Length
Copper (Cu) ------ 6.50" (165 mm)
Cable Range Requirements
Kit Number Cable Insulation Conductor
O.D. Range Size Range
5797A-MT 1.07" to 1.70" 1/0 AWG - 350 kcmil*
(27,2 mm to 43,2 mm) (60 - 185 mm
2
)
3M
Cold Shrink
QS-III Splicing Kit
5797A-MT
78-8126-0432-6-A
ƽCAUTION
Working around energized high-voltage systems may cause serious
injury or death. Installation should be performed by personnel familiar
with good safety practice in handling high-voltage electrical equipment.
De-energize and ground all electrical systems before installing product.