3M 7624-T-110 Air Conditioner User Manual


 
2 78-8113-5099-6 Rev E
1.0 Kit Contents
3 High–K, Tracking Resistant, Silicone Rubber Terminations
3 Pre-formed Ground Braids
3 Constant Force Springs
3 3M
EMI Copper Foil Shielding Tape 1181 Strips, 1/2" x 10"
6 Strips Scotch
®
Mastic Strip 2230 (black with white release liners, bagged)
1 3M
Cable Cleaning Preparation Kit CC-2
1 Instruction Sheet
Note: Do not use knives to open plastic bags.
Kit Selection Table
NOTE: Final Determination Factor is cable insulation diameter.
Kit Number
Primary Insulation
O.D. Range Jacket O.D, Range
Conductor Size Range (AWG & kcmil)
5 kV 8 kV 15 kV
7622–T–110
0.64" – 1.08"
(16,3 – 27,4 mm)
0.97" – 1.48"
(24,6 – 37,7 mm)
4/0 – 400
3/0 – 300
2 – 2/0
(35 – 70 mm
2
)
7623–T–110
0.72" – 1.29"
(18,3 – 32,8 mm)
1.04" – 1.60"
(26,4 – 40,6 mm)
300 – 500
250 – 500
2/0 – 300
(70 – 150 mm
2
)
7624–T–110
0.83" – 1.53"
(21,1 – 38,9 mm)
1.12" – 1.87"
(28,4 – 47,5 mm)
500 – 750
350 – 700
4/0 – 500
(120 – 240 mm
2
)
7625–T–110
1.05" – 1.80"
(26,7 – 45,7 mm)
1.39" – 2.40"
(35,2 – 61,0 mm)
700 – 1500
600 – 1250
500 – 1000
(240 – 500 mm
2
)
7626–T–110
1.53" – 2.32"
(38,9 – 58,9 mm)
1.84" – 2.80"
(46,7 – 71,1 mm)
1750 – 2000
1500 – 2000
1250 – 2000
(625 – 1000 mm
2
)
Table 1