12.4 Remove constant force spring. Bend shield wires back upon cable jacket 1-1/2" (38 mm). Cut excess shield wire and
discard (Figure 17).
9" (229 mm)
1-1/2" (38 mm)
Semi-Conductive Jacket
Fold Back Shield Wires
Depth Of Terminal Lug + Growth Allowance
Figure 17
12.5 Remove semi-conductive jacket to dimension shown in Figure 18.
NOTE: To ease jacket removal, install constant force spring as shown in Figure 18 and ring-cut 80% through jacket.
Remove jacket sections by pulling against constant force spring. DO NOT BELL SEMI-CON JACKET. Remove
constant force spring.
NOTE: It is imperative to remove all remnants of the semi-conductive jacket, even if the semi-conductive jacket comes
off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer.
Depth Of Terminal Lug + Growth Allowance
6" (152 mm)
1-1/2"
(38 mm)
Semi-Conductive Jacket
Cut Line
Constant Force Spring
Fold Back Shield Wires
1-1/2" (38 mm)
Figure 18