A SERVICE OF

logo

YORK INTERNATIONAL
67
FORM 150.64-EG1
MODEL
YCAL
VOLT
MCA
1
MIN
N/F DISC
SW
2
D.E. FUSE CKT. BKR.
5
FIELD WIRING LUGS
6
FIELD WIRING LUGS
6
FIELD WIRING LUGS
6
SYSTEM #1 COMPRESSOR & FAN SYSTEM #2 COMPRESSOR & FAN
TERMINAL BLOCK (std) NF DISC. SWITCH (opt) CIRCUIT BREAKER (opt) COMPR. #1 COMPR. #2 FANS COMPR. #1 COMPR. #2 FANS
REC. MAX
4
REC. MAX
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE RLA LRA RLA LRA QTY
FLA
(EA)
RLA LRA RLA LRA QTY
FLA
(EA)
0041
380/415 90 100 100 100 100 100 1 6awg - 500MCM 1 6awg - 350MCM 1 6awg - 350MCM 17.2 125 17.2 125 2 4 17.2 125 17.2 125 2 4
0045
380/415 91 100 100 100 100 100 1 6awg - 500MCM 1 6awg - 350MCM 1 6awg - 350MCM 17.6 125 17.6 125 2 4 17.2 125 17.2 125 2 4
0051
380/415 103 150 110 110 110 110 1 6awg - 500MCM 1 6awg - 350MCM 1 6awg - 350MCM 17.6 158 17.6 158 2 4 21.8 127 23.7 187 2 4
0055
380/415 113 150 125 125 125 125 1 6awg - 500MCM 1 6awg - 350MCM 1 6awg - 350MCM 23.7 187 21.8 127 2 4 21.8 127 23.7 187 2 4
0061
380/415 124 150 150 150 150 150 1 6awg - 500MCM 1 6awg - 350MCM 1 6awg - 350MCM 30.1 225 23.7 198 2 4 23.7 167 23.7 167 2 4
0065
380/415 132 150 150 150 150 150 1 6awg - 500MCM 1 6awg - 350MCM 1 6awg - 350MCM 30.1 225 30.1 225 2 4 23.7 198 23.7 198 2 4
YCAL0041 - YCAL0065
SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 2)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Discon
-
nect Switch (optional) or Circuit Breaker (optional).)