TX Series 48 - 1250A
Setpoint
Security
Description
Factory Setting
Range Setting
Imbalance Alarm Level 15% FLA 5-30 %, Off
Imbalance Alarm Delay 1.5 sec 1.0-20.0 sec
Imbalance Trip Level 20% 5-30 %, Off
Imbalance Trip Delay 2.0 sec 1.0-20.0 sec
Undercurrent Alarm Level Off 10-90 %, Off
Undercurrent Alarm Delay 2.0 sec 1.0-60.0 sec
Overcurrent Alarm Level Off 100-300 %, Off
Overcurrent Alarm Delay 2.0 sec 1.0-20.0 sec
Overcurrent Trip Level Off 100-300 %, Off
Overcurrent Trip Delay 2.0 sec 1.0-20.0 sec
Phase Loss Trip Disabled Enabled or Disabled
Phase Loss Trip Delay 0.1 sec 0-20.0 sec
Phase Rotation Detection Enabled Enabled Only
Phase Rotation ABC ABC
Ground Fault Alarm Level Off 5-90 %, Off
Ground Fault Alarm Delay 0.1 sec 0.1-20.0 sec
Ground Fault Loset Trip Level Off 5-90 %, Off
Ground Fault Loset Trip Delay 0.5 sec 0.1-20 sec
Ground Fault Hiset Trip Level Off 5-90 %, Off
Ground Fault Hiset Trip Delay 0.008 sec 0.008-0.250 sec
Overvoltage Alarm Level Off 5 -30%, Off
Overvoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Overvoltage Trip Level Off 5-30%, Off
Overvoltage Trip Delay 2.0 sec 1.0-30.0 sec
Undervoltage Alarm Level Off 5-30%, Off
Undervoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Undervoltage Trip Level Off 5-30%, Off
Undervoltage Trip Delay 2.0 sec 1.0-30.0 sec
Line Frequency Trip Window Disabled 0-6 Hz, Disabled
Line Frequency Trip Delay 1.0 sec 1.0-20.0 sec
P/F Lead P/F Alarm Off 0.1-1.00, Off
P/F Lead Alarm Delay 1.0 sec 1-120 sec
P/F Lead P/F Trip Off .01-1.00, Off
P/F Lead Trip Delay 1.0 sec 1-120 sec
P/F Lag P/F Alarm Off .01-1.00, Off
P/F Lag Alarm Delay 1.0 sec 1-120 sec
P/F Lag P/F Trip Off .01-1.00, Off
P/F Lag Trip Delay 1.0 sec 1-120 sec
Power Demand Period 10 min 1 - 60 min
KW Demand Alarm Pickup Off KW Off, 1-100000
KVA Demand Alarm Pickup Off KVA Off, 1-100000
KVAR Demand Alarm Pickup Off KVAR Off, 1-100000
Amps Demand Alarm Pickup Off Amps Off, 1-100000
Page 3
Phase and Ground Settings
Level 2
Password Protection