SP.3 Phase & Ground Settings (Setpoint Page 3)
(Security Level: 2)
Note: Proper phase sequence must be observed when
connecting the input power. For example, phase A
must lead phase B, which in turn must lead phase
C by 120° respectively. If the phase rotation is not
correct, a fault light and the LCD display will
indicate the problem.
SP3.1 Imbalance Alarm Level: This is an advance
warning of a phase imbalance problem. The
problem may not be a fault in the motor, but merely
caused by imbalanced voltages.
Imbalance Alarm Delay: The amount of time the
imbalance condition must exist before an alarm
occurs.
SP3.2 Imbalance Trip Level: This will trip the motor on
excessive phase imbalance. The trip level should
be programmed to a higher value than the alarm
level.
Imbalance Trip Delay: The amount of time the
imbalance condition must exist before a trip will
occur.
SP3.3 Undercurrent Alarm Level: Typically used to
warn of possible load loss, a coupling breaking or
other mechanical problems.
Undercurrent Alarm Delay: The amount of time
the undercurrent condition must exist before an
alarm will occur.
SP3.4 Overcurrent Alarm Level: Typically used to
indicate when the motor is overloaded. This feature
can be used to either stop the feed to the
equipment or warn operators of an overload
condition.
Overcurrent Alarm Delay: The amount of time
the overcurrent condition must exist before an
alarm will occur.
MENU
PAGE 3 PHASE &
GROUND SETTINGS
IMBALANCE ALARM
LEVEL: 15% FLA
Range: 5 - 30%, OFF
Increments of 1
(Hit DOWN ARROW two times)
IMBALANCE ALARM
DELAY: 1.5 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
IMBALANCE TRIP
LEVEL: 20%FLA
OVERCURRENT ALARM
LEVEL: OFF
Range: 5 - 30%, OFF
Increments of 1
Range: 100 - 300%, OFF
Increments of 1
IMBALANCE TRIP
DELAY: 2.0 SEC.
OVERCURRENT ALARM
DELAY: 2.0 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
Range: 1.0 - 20.0 SEC., OFF
Increments of 0.1
OVERCURRENT TRIP
LEVEL: OFF
PHASE LOSS TRIP
: DISABLED
Range: 100 - 300%, OFF
Increments of 1
Options: Enabled or Disabled
OVERCURRENT TRIP
DELAY: 2.0 SEC.
PHASE LOSS TRIP
DELAY: 0.1 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
Range: 0 - 20.0 SEC.
Increments of 0.1
UNDERCURRENT ALARM
LEVEL: OFF
Range: 10 - 90%, OFF
Increments of 1
UNDERCURRENT ALARM
DELAY: 2.0 SEC.
Range: 1.0 - 60.0 SEC.
Increments of 0.1
PHASE ROTATION
DETECTION: DISABLED
GROUND FAULT LOSET
TRIP LEVEL: OFF
Options: Enabled or Disabled Options: ABC, ACB
Range: 5 - 90%, OFF
Increments of 1
PHASE ROTATION
: ABC
GROUND FAULT LOSET
TRIP DELAY: 0.5 SEC
Range: 1.0 - 20.0 SEC., OFF
Increments of 0.1
GROUND FAULT HISET
TRIP LEVEL: OFF
Range: 5 - 90%, OFF
Increments of 1
GROUND FAULT HISET
TRIP DELAY: 0.008 SEC.
Range: 0.008 - 0.250 SEC.
Increments of 0.002
GROUND FAULT ALARM
LEVEL: OFF
Range: 5 - 90%, OFF
Increments of 1
GROUND FAULT ALARM
DELAY: 0.1 SEC.
Range: 0.5 - 20.0 SEC.
Increments of 0.1
OVERVOLTAGE ALARM
LEVEL: OFF
OVERVOLTAGE ALARM
DELAY: 1.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
OVERVOLTAGE TRIP
LEVEL: OFF
OVERVOLTAGE TRIP
DELAY: 2.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
UNDERVOLTAGE ALARM
LEVEL: OFF
UNDERVOLTAGE ALARM
DELAY: 1.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
UNDERVOLTAGE TRIP
LEVEL: OFF
UNDERVOLTAGE TRIP
DELAY: 2.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
LINE FREQUENCY TRIP
WINDOW: DISABLED
LINE FREQUENCY TRIP
DELAY: 1.0 SEC.
Range: 0 - 6, Disabled
Increments of 1
Range: 1.0 - 20.0 SEC.
Increments of 0.1