TOSHIBA- 81
TX Series 48 - 1250A
Appendix B - Record of Setpoint Adjustments
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Setting
Motor Full Load Amps (FLA) Model dependent
50 - 100% of Unit Max Current Rating (Model
and Service Factor dependent)
Service Factor 1.15 1.00 – 1.3
Overload Class 10 O/L Class 5-30
NEMA Design B A-F
Insulation Class B A, B, C, E, F, H, K, N, S
Line Voltage 480 208 to 600
Line Frequency 60 50 or 60 HZ
Page 1
Basic Configuration
Level 1
No Passowrd Required
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Setting
Start Control Mode Start Ramp 1
Jog, Start Ramp 1, Start Ramp 2, Custom
Accel Curve, Start Disabled, Dual Ramp
Jog Voltage Off 5-75%, Off
Start Ramp #1 Type Voltage Current, Voltage, Off
Initial Voltage #1 20% 0-100%
Ramp Time #1 10 sec 0-120 sec
Current Limit #1 350% FLA 200-600 %
Initial Current #1 200% FLA 0-300%
Ramp Time #1 10 sec 0-120 sec
Maximum Current #1 350% FLA 200-600 %
Start Ramp #2 Type Off Current, Voltage, Off
Initial Voltage #2 60% 0-100 %
Ramp Time #2 10 sec 0-120 sec
Current Limit #2 350 % FLA 200-600 %
Initial Current #2 200% FLA 0-600 %
Ramp Time #2 10 sec 0-120 sec
Maximum Current #2 350% FLA 200-600 %
Kick Start Type Off Voltage or Off
Kick Start Voltage 65% 10-100 %
Kick Start Time 0.50 sec 0.10-2.00
Deceleration Disabled Enabled or Disabled
Start Deceleration Voltage 60% 0-100 %
Stop Deceleration Voltage 30% 0-59 %
Deceleration Time 5 sec 1-60 sec
Timed Output Time Off 1-1000 sec, Off
Run Delay Time 1 Sec 1-30 sec, Off
At Speed Delay Time 1 Sec 1-30 sec, Off
Bypass Pull-in Current 100% FLA 90 - 300%
Page 2
Starter Configuration
Level 1
No Passowrd Required