COMMUNICATION INTERFACE
REMOTE CONTACTS (IBM AS/400)
The remote contacts interface is a standard feature. It is provided through
solid state relays with contacts through a DB9 male connector located on the
back of the UPS. The following chart shows the signals and the connector
pinout.
Pin Signal Function Logic In the UPS
1 Fault Signal Closed when fault
detected
2 UPS stop com-
mon
Backup stop when the
level changes from
Low (-3 to -15 V) to
High (+3 to +15 V)
3 UPS stop signal
input
4 Normal input
power supply
Closed with normal
supply power
5 Signal common Common signal return
6 Bypass operation Closed during bypass
operation
7 Battery voltage
low
Closed at voltage drop
8 UPS operation Closed during inverter
operation
9 Power failure
signal
Closed at power failure
Voltage Current
48 VDC peak 100 mA peak
30 VAC rms
(42 VAC peak)
70 mA rms
(100 mA peak)