9.3 Power Range 6000 VA (208/240 V)
1000 Series 6kVA Specification
UT1G1G060C6RKB3 + UT1-BR-0607
General
Topology
True on-line, Double conversion, IGBT Power Factor Correction
Input
Single Phase - 208/240Vin
Frequency Synchronization
Cold Start (0 to 100% load)
Default Output Frequency 60 Hz
+10/-15% of nominal (default)
Battery Mode/Free Run Mode
Sine wave, zero transfer time
Greater than 89% at Nominal Voltage
High Efficiency Mode Efficiency
Rated Current (based on 240V)
Inverter Overload Capacity
125% for 1 min, 150% for 10 sec
Voltage Transient Response
(battery mode with R type load)
Voltage Transient Recovery (R
type Load)
Return to nominal voltage within 30 ms
On-line Transfer Time – Inverter to
Bypass and Bypass to Inverter
Less than 4m sec
High Efficiency Transfer Time –
Inverter to Bypass and Bypass to
Less than 4m sec transfer time
Electronic overload and short circuit.
Voltage Total Harmonic Distortion
(Full Linear Load)
Less than 3 % THD
Voltage Total Harmonic Distortion
(Full Non-Linear Load)
Less than 5 % THD
Steady State Output Voltage
Regulation
No-load to Full-load +/- 2% at full battery.